Kabelarea för 5 Ampere vid 60 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 5 A över 60 m vid 400V.

Copper Cable (≤3% Drop)1.5 mm²Drop: 7.41V (1.85%)
Aluminum Cable (≤3% Drop)2.5 mm²Drop: 7.34V (1.83%)
Voltage at Load392.6 VLine Loss: 64.2 W
Max Power & Breaker3.46 kW6A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 5A at 60m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A7.41 V (1.85%)392.6 V12.23 V (3.06%)64.2 W✓ OK (≤3%)
2.5 mm²24 A18 A4.45 V (1.11%)395.6 V7.34 V (1.83%)38.5 W✓ OK (≤3%)
4 mm²32 A25 A2.78 V (0.69%)397.2 V4.59 V (1.15%)24.1 W✓ OK (≤3%)
6 mm²41 A32 A1.85 V (0.46%)398.1 V3.06 V (0.76%)16.1 W✓ OK (≤3%)
10 mm²57 A44 A1.11 V (0.28%)398.9 V1.83 V (0.46%)9.6 W✓ OK (≤3%)
16 mm²76 A59 A0.69 V (0.17%)399.3 V1.15 V (0.29%)6.0 W✓ OK (≤3%)
25 mm²101 A78 A0.44 V (0.11%)399.6 V0.73 V (0.18%)3.9 W✓ OK (≤3%)
35 mm²125 A97 A0.32 V (0.08%)399.7 V0.52 V (0.13%)2.8 W✓ OK (≤3%)
50 mm²151 A118 A0.22 V (0.06%)399.8 V0.37 V (0.09%)1.9 W✓ OK (≤3%)
70 mm²192 A150 A0.16 V (0.04%)399.8 V0.26 V (0.07%)1.4 W✓ OK (≤3%)
95 mm²232 A181 A0.12 V (0.03%)399.9 V0.19 V (0.05%)1.0 W✓ OK (≤3%)
120 mm²269 A210 A0.09 V (0.02%)399.9 V0.15 V (0.04%)0.8 W✓ OK (≤3%)
150 mm²309 A241 A0.07 V (0.02%)399.9 V0.12 V (0.03%)0.6 W✓ OK (≤3%)
185 mm²353 A275 A0.06 V (0.02%)399.9 V0.1 V (0.02%)0.5 W✓ OK (≤3%)
240 mm²415 A324 A0.05 V (0.01%)400.0 V0.08 V (0.02%)0.4 W✓ OK (≤3%)
300 mm²477 A372 A0.04 V (0.01%)400.0 V0.06 V (0.02%)0.3 W✓ OK (≤3%)
400 mm²570 A445 A0.03 V (0.01%)400.0 V0.05 V (0.01%)0.2 W✓ OK (≤3%)

FAQ — Kabelarea för 5 Ampere vid 60 Meter (400V)

Vilken kabelarea krävs för 5A vid 60 meter (400V)?

För 5 Ampere över 60 meter vid 400V rekommenderas 1.5 mm² kopparkabel för att hålla spänningsfallet under 3% (7.41V / 1.85%).

Hur stor effekt motsvarar 5A vid 400V?

Det motsvarar 3.46 kW med en rekommenderad säkring på 6A.