Kabelarea för 5 Ampere vid 45 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 5 A över 45 m vid 400V.

Copper Cable (≤3% Drop)1.5 mm²Drop: 5.56V (1.39%)
Aluminum Cable (≤3% Drop)1.5 mm²Drop: 9.17V (2.29%)
Voltage at Load394.4 VLine Loss: 48.1 W
Max Power & Breaker3.46 kW6A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 5A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A5.56 V (1.39%)394.4 V9.17 V (2.29%)48.1 W✓ OK (≤3%)
2.5 mm²24 A18 A3.34 V (0.83%)396.7 V5.5 V (1.38%)28.9 W✓ OK (≤3%)
4 mm²32 A25 A2.08 V (0.52%)397.9 V3.44 V (0.86%)18.1 W✓ OK (≤3%)
6 mm²41 A32 A1.39 V (0.35%)398.6 V2.29 V (0.57%)12.0 W✓ OK (≤3%)
10 mm²57 A44 A0.83 V (0.21%)399.2 V1.38 V (0.34%)7.2 W✓ OK (≤3%)
16 mm²76 A59 A0.52 V (0.13%)399.5 V0.86 V (0.21%)4.5 W✓ OK (≤3%)
25 mm²101 A78 A0.33 V (0.08%)399.7 V0.55 V (0.14%)2.9 W✓ OK (≤3%)
35 mm²125 A97 A0.24 V (0.06%)399.8 V0.39 V (0.1%)2.1 W✓ OK (≤3%)
50 mm²151 A118 A0.17 V (0.04%)399.8 V0.28 V (0.07%)1.4 W✓ OK (≤3%)
70 mm²192 A150 A0.12 V (0.03%)399.9 V0.2 V (0.05%)1.0 W✓ OK (≤3%)
95 mm²232 A181 A0.09 V (0.02%)399.9 V0.14 V (0.04%)0.8 W✓ OK (≤3%)
120 mm²269 A210 A0.07 V (0.02%)399.9 V0.11 V (0.03%)0.6 W✓ OK (≤3%)
150 mm²309 A241 A0.06 V (0.01%)399.9 V0.09 V (0.02%)0.5 W✓ OK (≤3%)
185 mm²353 A275 A0.05 V (0.01%)400.0 V0.07 V (0.02%)0.4 W✓ OK (≤3%)
240 mm²415 A324 A0.03 V (0.01%)400.0 V0.06 V (0.01%)0.3 W✓ OK (≤3%)
300 mm²477 A372 A0.03 V (0.01%)400.0 V0.05 V (0.01%)0.2 W✓ OK (≤3%)
400 mm²570 A445 A0.02 V (0.01%)400.0 V0.03 V (0.01%)0.2 W✓ OK (≤3%)

FAQ — Kabelarea för 5 Ampere vid 45 Meter (400V)

Vilken kabelarea krävs för 5A vid 45 meter (400V)?

För 5 Ampere över 45 meter vid 400V rekommenderas 1.5 mm² kopparkabel för att hålla spänningsfallet under 3% (5.56V / 1.39%).

Hur stor effekt motsvarar 5A vid 400V?

Det motsvarar 3.46 kW med en rekommenderad säkring på 6A.