Kabelarea för 550 Ampere vid 100 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 550 A över 100 m vid 230V.
Copper Cable (≤3% Drop)400 mm²Drop: 5.88V (2.56%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 9.71V (4.22%)
Voltage at Load224.1 VLine Loss: 3236.7 W
Max Power & Breaker126.5 kW600A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 100m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 1569.33 V (682.32%) | 0.0 V | 2588.67 V (1125.51%) | 863133.3 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 941.6 V (409.39%) | 0.0 V | 1553.2 V (675.3%) | 517880.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 588.5 V (255.87%) | 0.0 V | 970.75 V (422.07%) | 323675.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 392.33 V (170.58%) | 0.0 V | 647.17 V (281.38%) | 215783.3 W | Drop High |
| 10 mm² | 57 A | 44 A | 235.4 V (102.35%) | 0.0 V | 388.3 V (168.83%) | 129470.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 147.12 V (63.97%) | 82.9 V | 242.69 V (105.52%) | 80918.7 W | Drop High |
| 25 mm² | 101 A | 78 A | 94.16 V (40.94%) | 135.8 V | 155.32 V (67.53%) | 51788.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 67.26 V (29.24%) | 162.7 V | 110.94 V (48.24%) | 36991.4 W | Drop High |
| 50 mm² | 151 A | 118 A | 47.08 V (20.47%) | 182.9 V | 77.66 V (33.77%) | 25894.0 W | Drop High |
| 70 mm² | 192 A | 150 A | 33.63 V (14.62%) | 196.4 V | 55.47 V (24.12%) | 18495.7 W | Drop High |
| 95 mm² | 232 A | 181 A | 24.78 V (10.77%) | 205.2 V | 40.87 V (17.77%) | 13628.4 W | Drop High |
| 120 mm² | 269 A | 210 A | 19.62 V (8.53%) | 210.4 V | 32.36 V (14.07%) | 10789.2 W | Drop High |
| 150 mm² | 309 A | 241 A | 15.69 V (6.82%) | 214.3 V | 25.89 V (11.26%) | 8631.3 W | Drop High |
| 185 mm² | 353 A | 275 A | 12.72 V (5.53%) | 217.3 V | 20.99 V (9.13%) | 6998.4 W | Drop High |
| 240 mm² | 415 A | 324 A | 9.81 V (4.26%) | 220.2 V | 16.18 V (7.03%) | 5394.6 W | Drop High |
| 300 mm² | 477 A | 372 A | 7.85 V (3.41%) | 222.2 V | 12.94 V (5.63%) | 4315.7 W | Drop High |
| 400 mm² | 570 A | 445 A | 5.88 V (2.56%) | 224.1 V | 9.71 V (4.22%) | 3236.7 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 550 Ampere vid 100 Meter (230V)
Vilken kabelarea krävs för 550A vid 100 meter (230V)?
För 550 Ampere över 100 meter vid 230V rekommenderas 400 mm² kopparkabel för att hålla spänningsfallet under 3% (5.88V / 2.56%).
Hur stor effekt motsvarar 550A vid 230V?
Det motsvarar 126.5 kW med en rekommenderad säkring på 600A.
Related Lengths & Currents (230V)
550A · 5m (230V)550A · 10m (230V)550A · 15m (230V)550A · 20m (230V)550A · 25m (230V)550A · 30m (230V)550A · 35m (230V)550A · 40m (230V)550A · 45m (230V)550A · 50m (230V)550A · 60m (230V)550A · 70m (230V)10A · 100m (230V)16A · 100m (230V)20A · 100m (230V)25A · 100m (230V)32A · 100m (230V)40A · 100m (230V)50A · 100m (230V)63A · 100m (230V)80A · 100m (230V)100A · 100m (230V)125A · 100m (230V)160A · 100m (230V)200A · 100m (230V)