⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 550 Ampere vid 100 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 550 A över 100 m vid 230V.

Copper Cable (≤3% Drop)400 mm²Drop: 5.88V (2.56%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 9.71V (4.22%)
Voltage at Load224.1 VLine Loss: 3236.7 W
Max Power & Breaker126.5 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1569.33 V (682.32%)0.0 V2588.67 V (1125.51%)863133.3 WDrop High
2.5 mm²24 A18 A941.6 V (409.39%)0.0 V1553.2 V (675.3%)517880.0 WDrop High
4 mm²32 A25 A588.5 V (255.87%)0.0 V970.75 V (422.07%)323675.0 WDrop High
6 mm²41 A32 A392.33 V (170.58%)0.0 V647.17 V (281.38%)215783.3 WDrop High
10 mm²57 A44 A235.4 V (102.35%)0.0 V388.3 V (168.83%)129470.0 WDrop High
16 mm²76 A59 A147.12 V (63.97%)82.9 V242.69 V (105.52%)80918.7 WDrop High
25 mm²101 A78 A94.16 V (40.94%)135.8 V155.32 V (67.53%)51788.0 WDrop High
35 mm²125 A97 A67.26 V (29.24%)162.7 V110.94 V (48.24%)36991.4 WDrop High
50 mm²151 A118 A47.08 V (20.47%)182.9 V77.66 V (33.77%)25894.0 WDrop High
70 mm²192 A150 A33.63 V (14.62%)196.4 V55.47 V (24.12%)18495.7 WDrop High
95 mm²232 A181 A24.78 V (10.77%)205.2 V40.87 V (17.77%)13628.4 WDrop High
120 mm²269 A210 A19.62 V (8.53%)210.4 V32.36 V (14.07%)10789.2 WDrop High
150 mm²309 A241 A15.69 V (6.82%)214.3 V25.89 V (11.26%)8631.3 WDrop High
185 mm²353 A275 A12.72 V (5.53%)217.3 V20.99 V (9.13%)6998.4 WDrop High
240 mm²415 A324 A9.81 V (4.26%)220.2 V16.18 V (7.03%)5394.6 WDrop High
300 mm²477 A372 A7.85 V (3.41%)222.2 V12.94 V (5.63%)4315.7 WDrop High
400 mm²570 A445 A5.88 V (2.56%)224.1 V9.71 V (4.22%)3236.7 W✓ OK (≤3%)

FAQ — Kabelarea för 550 Ampere vid 100 Meter (230V)

Vilken kabelarea krävs för 550A vid 100 meter (230V)?

För 550 Ampere över 100 meter vid 230V rekommenderas 400 mm² kopparkabel för att hålla spänningsfallet under 3% (5.88V / 2.56%).

Hur stor effekt motsvarar 550A vid 230V?

Det motsvarar 126.5 kW med en rekommenderad säkring på 600A.