Kabelarea för 550 Ampere vid 5 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 550 A över 5 m vid 230V.

Copper Cable (≤3% Drop)400 mm²Drop: 0.29V (0.13%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.49V (0.21%)
Voltage at Load229.7 VLine Loss: 161.8 W
Max Power & Breaker126.5 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A78.47 V (34.12%)151.5 V129.43 V (56.28%)43156.7 WDrop High
2.5 mm²24 A18 A47.08 V (20.47%)182.9 V77.66 V (33.77%)25894.0 WDrop High
4 mm²32 A25 A29.43 V (12.79%)200.6 V48.54 V (21.1%)16183.8 WDrop High
6 mm²41 A32 A19.62 V (8.53%)210.4 V32.36 V (14.07%)10789.2 WDrop High
10 mm²57 A44 A11.77 V (5.12%)218.2 V19.41 V (8.44%)6473.5 WDrop High
16 mm²76 A59 A7.36 V (3.2%)222.6 V12.13 V (5.28%)4045.9 WDrop High
25 mm²101 A78 A4.71 V (2.05%)225.3 V7.77 V (3.38%)2589.4 WDrop High
35 mm²125 A97 A3.36 V (1.46%)226.6 V5.55 V (2.41%)1849.6 WDrop High
50 mm²151 A118 A2.35 V (1.02%)227.6 V3.88 V (1.69%)1294.7 WDrop High
70 mm²192 A150 A1.68 V (0.73%)228.3 V2.77 V (1.21%)924.8 WDrop High
95 mm²232 A181 A1.24 V (0.54%)228.8 V2.04 V (0.89%)681.4 WDrop High
120 mm²269 A210 A0.98 V (0.43%)229.0 V1.62 V (0.7%)539.5 WDrop High
150 mm²309 A241 A0.78 V (0.34%)229.2 V1.29 V (0.56%)431.6 WDrop High
185 mm²353 A275 A0.64 V (0.28%)229.4 V1.05 V (0.46%)349.9 WDrop High
240 mm²415 A324 A0.49 V (0.21%)229.5 V0.81 V (0.35%)269.7 WDrop High
300 mm²477 A372 A0.39 V (0.17%)229.6 V0.65 V (0.28%)215.8 WDrop High
400 mm²570 A445 A0.29 V (0.13%)229.7 V0.49 V (0.21%)161.8 W✓ OK (≤3%)

FAQ — Kabelarea för 550 Ampere vid 5 Meter (230V)

Vilken kabelarea krävs för 550A vid 5 meter (230V)?

För 550 Ampere över 5 meter vid 230V rekommenderas 400 mm² kopparkabel för att hålla spänningsfallet under 3% (0.29V / 0.13%).

Hur stor effekt motsvarar 550A vid 230V?

Det motsvarar 126.5 kW med en rekommenderad säkring på 600A.