⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 550 Ampere vid 30 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 550 A över 30 m vid 230V.

Copper Cable (≤3% Drop)400 mm²Drop: 1.77V (0.77%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.91V (1.27%)
Voltage at Load228.2 VLine Loss: 971.0 W
Max Power & Breaker126.5 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 30m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A470.8 V (204.7%)0.0 V776.6 V (337.65%)258940.0 WDrop High
2.5 mm²24 A18 A282.48 V (122.82%)0.0 V465.96 V (202.59%)155364.0 WDrop High
4 mm²32 A25 A176.55 V (76.76%)53.4 V291.22 V (126.62%)97102.5 WDrop High
6 mm²41 A32 A117.7 V (51.17%)112.3 V194.15 V (84.41%)64735.0 WDrop High
10 mm²57 A44 A70.62 V (30.7%)159.4 V116.49 V (50.65%)38841.0 WDrop High
16 mm²76 A59 A44.14 V (19.19%)185.9 V72.81 V (31.65%)24275.6 WDrop High
25 mm²101 A78 A28.25 V (12.28%)201.8 V46.6 V (20.26%)15536.4 WDrop High
35 mm²125 A97 A20.18 V (8.77%)209.8 V33.28 V (14.47%)11097.4 WDrop High
50 mm²151 A118 A14.12 V (6.14%)215.9 V23.3 V (10.13%)7768.2 WDrop High
70 mm²192 A150 A10.09 V (4.39%)219.9 V16.64 V (7.24%)5548.7 WDrop High
95 mm²232 A181 A7.43 V (3.23%)222.6 V12.26 V (5.33%)4088.5 WDrop High
120 mm²269 A210 A5.88 V (2.56%)224.1 V9.71 V (4.22%)3236.8 WDrop High
150 mm²309 A241 A4.71 V (2.05%)225.3 V7.77 V (3.38%)2589.4 WDrop High
185 mm²353 A275 A3.82 V (1.66%)226.2 V6.3 V (2.74%)2099.5 WDrop High
240 mm²415 A324 A2.94 V (1.28%)227.1 V4.85 V (2.11%)1618.4 WDrop High
300 mm²477 A372 A2.35 V (1.02%)227.6 V3.88 V (1.69%)1294.7 WDrop High
400 mm²570 A445 A1.77 V (0.77%)228.2 V2.91 V (1.27%)971.0 W✓ OK (≤3%)

FAQ — Kabelarea för 550 Ampere vid 30 Meter (230V)

Vilken kabelarea krävs för 550A vid 30 meter (230V)?

För 550 Ampere över 30 meter vid 230V rekommenderas 400 mm² kopparkabel för att hålla spänningsfallet under 3% (1.77V / 0.77%).

Hur stor effekt motsvarar 550A vid 230V?

Det motsvarar 126.5 kW med en rekommenderad säkring på 600A.