Kabelarea för 550 Ampere vid 60 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 550 A över 60 m vid 230V.

Copper Cable (≤3% Drop)400 mm²Drop: 3.53V (1.54%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 5.82V (2.53%)
Voltage at Load226.5 VLine Loss: 1942.1 W
Max Power & Breaker126.5 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 60m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A941.6 V (409.39%)0.0 V1553.2 V (675.3%)517880.0 WDrop High
2.5 mm²24 A18 A564.96 V (245.63%)0.0 V931.92 V (405.18%)310728.0 WDrop High
4 mm²32 A25 A353.1 V (153.52%)0.0 V582.45 V (253.24%)194205.0 WDrop High
6 mm²41 A32 A235.4 V (102.35%)0.0 V388.3 V (168.83%)129470.0 WDrop High
10 mm²57 A44 A141.24 V (61.41%)88.8 V232.98 V (101.3%)77682.0 WDrop High
16 mm²76 A59 A88.28 V (38.38%)141.7 V145.61 V (63.31%)48551.2 WDrop High
25 mm²101 A78 A56.5 V (24.56%)173.5 V93.19 V (40.52%)31072.8 WDrop High
35 mm²125 A97 A40.35 V (17.55%)189.6 V66.57 V (28.94%)22194.9 WDrop High
50 mm²151 A118 A28.25 V (12.28%)201.8 V46.6 V (20.26%)15536.4 WDrop High
70 mm²192 A150 A20.18 V (8.77%)209.8 V33.28 V (14.47%)11097.4 WDrop High
95 mm²232 A181 A14.87 V (6.46%)215.1 V24.52 V (10.66%)8177.1 WDrop High
120 mm²269 A210 A11.77 V (5.12%)218.2 V19.41 V (8.44%)6473.5 WDrop High
150 mm²309 A241 A9.42 V (4.09%)220.6 V15.53 V (6.75%)5178.8 WDrop High
185 mm²353 A275 A7.63 V (3.32%)222.4 V12.59 V (5.48%)4199.0 WDrop High
240 mm²415 A324 A5.88 V (2.56%)224.1 V9.71 V (4.22%)3236.8 WDrop High
300 mm²477 A372 A4.71 V (2.05%)225.3 V7.77 V (3.38%)2589.4 WDrop High
400 mm²570 A445 A3.53 V (1.54%)226.5 V5.82 V (2.53%)1942.1 W✓ OK (≤3%)

FAQ — Kabelarea för 550 Ampere vid 60 Meter (230V)

Vilken kabelarea krävs för 550A vid 60 meter (230V)?

För 550 Ampere över 60 meter vid 230V rekommenderas 400 mm² kopparkabel för att hålla spänningsfallet under 3% (3.53V / 1.54%).

Hur stor effekt motsvarar 550A vid 230V?

Det motsvarar 126.5 kW med en rekommenderad säkring på 600A.