Kabelarea för 550 Ampere vid 25 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 550 A över 25 m vid 230V.

Copper Cable (≤3% Drop)400 mm²Drop: 1.47V (0.64%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.43V (1.06%)
Voltage at Load228.5 VLine Loss: 809.2 W
Max Power & Breaker126.5 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A392.33 V (170.58%)0.0 V647.17 V (281.38%)215783.3 WDrop High
2.5 mm²24 A18 A235.4 V (102.35%)0.0 V388.3 V (168.83%)129470.0 WDrop High
4 mm²32 A25 A147.12 V (63.97%)82.9 V242.69 V (105.52%)80918.7 WDrop High
6 mm²41 A32 A98.08 V (42.64%)131.9 V161.79 V (70.34%)53945.8 WDrop High
10 mm²57 A44 A58.85 V (25.59%)171.2 V97.07 V (42.21%)32367.5 WDrop High
16 mm²76 A59 A36.78 V (15.99%)193.2 V60.67 V (26.38%)20229.7 WDrop High
25 mm²101 A78 A23.54 V (10.23%)206.5 V38.83 V (16.88%)12947.0 WDrop High
35 mm²125 A97 A16.81 V (7.31%)213.2 V27.74 V (12.06%)9247.9 WDrop High
50 mm²151 A118 A11.77 V (5.12%)218.2 V19.41 V (8.44%)6473.5 WDrop High
70 mm²192 A150 A8.41 V (3.66%)221.6 V13.87 V (6.03%)4623.9 WDrop High
95 mm²232 A181 A6.19 V (2.69%)223.8 V10.22 V (4.44%)3407.1 WDrop High
120 mm²269 A210 A4.9 V (2.13%)225.1 V8.09 V (3.52%)2697.3 WDrop High
150 mm²309 A241 A3.92 V (1.71%)226.1 V6.47 V (2.81%)2157.8 WDrop High
185 mm²353 A275 A3.18 V (1.38%)226.8 V5.25 V (2.28%)1749.6 WDrop High
240 mm²415 A324 A2.45 V (1.07%)227.5 V4.04 V (1.76%)1348.6 WDrop High
300 mm²477 A372 A1.96 V (0.85%)228.0 V3.24 V (1.41%)1078.9 WDrop High
400 mm²570 A445 A1.47 V (0.64%)228.5 V2.43 V (1.06%)809.2 W✓ OK (≤3%)

FAQ — Kabelarea för 550 Ampere vid 25 Meter (230V)

Vilken kabelarea krävs för 550A vid 25 meter (230V)?

För 550 Ampere över 25 meter vid 230V rekommenderas 400 mm² kopparkabel för att hålla spänningsfallet under 3% (1.47V / 0.64%).

Hur stor effekt motsvarar 550A vid 230V?

Det motsvarar 126.5 kW med en rekommenderad säkring på 600A.