Kabelarea för 550 Ampere vid 10 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 550 A över 10 m vid 230V.
Copper Cable (≤3% Drop)400 mm²Drop: 0.59V (0.26%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.97V (0.42%)
Voltage at Load229.4 VLine Loss: 323.7 W
Max Power & Breaker126.5 kW600A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 10m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 156.93 V (68.23%) | 73.1 V | 258.87 V (112.55%) | 86313.3 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 94.16 V (40.94%) | 135.8 V | 155.32 V (67.53%) | 51788.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 58.85 V (25.59%) | 171.2 V | 97.07 V (42.21%) | 32367.5 W | Drop High |
| 6 mm² | 41 A | 32 A | 39.23 V (17.06%) | 190.8 V | 64.72 V (28.14%) | 21578.3 W | Drop High |
| 10 mm² | 57 A | 44 A | 23.54 V (10.23%) | 206.5 V | 38.83 V (16.88%) | 12947.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 14.71 V (6.4%) | 215.3 V | 24.27 V (10.55%) | 8091.9 W | Drop High |
| 25 mm² | 101 A | 78 A | 9.42 V (4.09%) | 220.6 V | 15.53 V (6.75%) | 5178.8 W | Drop High |
| 35 mm² | 125 A | 97 A | 6.73 V (2.92%) | 223.3 V | 11.09 V (4.82%) | 3699.1 W | Drop High |
| 50 mm² | 151 A | 118 A | 4.71 V (2.05%) | 225.3 V | 7.77 V (3.38%) | 2589.4 W | Drop High |
| 70 mm² | 192 A | 150 A | 3.36 V (1.46%) | 226.6 V | 5.55 V (2.41%) | 1849.6 W | Drop High |
| 95 mm² | 232 A | 181 A | 2.48 V (1.08%) | 227.5 V | 4.09 V (1.78%) | 1362.8 W | Drop High |
| 120 mm² | 269 A | 210 A | 1.96 V (0.85%) | 228.0 V | 3.24 V (1.41%) | 1078.9 W | Drop High |
| 150 mm² | 309 A | 241 A | 1.57 V (0.68%) | 228.4 V | 2.59 V (1.13%) | 863.1 W | Drop High |
| 185 mm² | 353 A | 275 A | 1.27 V (0.55%) | 228.7 V | 2.1 V (0.91%) | 699.8 W | Drop High |
| 240 mm² | 415 A | 324 A | 0.98 V (0.43%) | 229.0 V | 1.62 V (0.7%) | 539.5 W | Drop High |
| 300 mm² | 477 A | 372 A | 0.78 V (0.34%) | 229.2 V | 1.29 V (0.56%) | 431.6 W | Drop High |
| 400 mm² | 570 A | 445 A | 0.59 V (0.26%) | 229.4 V | 0.97 V (0.42%) | 323.7 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 550 Ampere vid 10 Meter (230V)
Vilken kabelarea krävs för 550A vid 10 meter (230V)?
För 550 Ampere över 10 meter vid 230V rekommenderas 400 mm² kopparkabel för att hålla spänningsfallet under 3% (0.59V / 0.26%).
Hur stor effekt motsvarar 550A vid 230V?
Det motsvarar 126.5 kW med en rekommenderad säkring på 600A.
Related Lengths & Currents (230V)
550A · 5m (230V)550A · 15m (230V)550A · 20m (230V)550A · 25m (230V)550A · 30m (230V)550A · 35m (230V)550A · 40m (230V)550A · 45m (230V)550A · 50m (230V)550A · 60m (230V)550A · 70m (230V)10A · 10m (230V)16A · 10m (230V)20A · 10m (230V)25A · 10m (230V)32A · 10m (230V)40A · 10m (230V)50A · 10m (230V)63A · 10m (230V)80A · 10m (230V)100A · 10m (230V)125A · 10m (230V)160A · 10m (230V)200A · 10m (230V)