Kabelarea för 550 Ampere vid 150 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 550 A över 150 m vid 400V.

Copper Cable (≤3% Drop)400 mm²Drop: 7.64V (1.91%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 12.61V (3.15%)
Voltage at Load392.4 VLine Loss: 7282.7 W
Max Power & Breaker381.05 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2038.62 V (509.66%)0.0 V3362.78 V (840.69%)1942050.0 WDrop High
2.5 mm²24 A18 A1223.17 V (305.79%)0.0 V2017.67 V (504.42%)1165230.0 WDrop High
4 mm²32 A25 A764.48 V (191.12%)0.0 V1261.04 V (315.26%)728268.8 WDrop High
6 mm²41 A32 A509.66 V (127.41%)0.0 V840.69 V (210.17%)485512.5 WDrop High
10 mm²57 A44 A305.79 V (76.45%)94.2 V504.42 V (126.1%)291307.5 WDrop High
16 mm²76 A59 A191.12 V (47.78%)208.9 V315.26 V (78.82%)182067.2 WDrop High
25 mm²101 A78 A122.32 V (30.58%)277.7 V201.77 V (50.44%)116523.0 WDrop High
35 mm²125 A97 A87.37 V (21.84%)312.6 V144.12 V (36.03%)83230.7 WDrop High
50 mm²151 A118 A61.16 V (15.29%)338.8 V100.88 V (25.22%)58261.5 WDrop High
70 mm²192 A150 A43.68 V (10.92%)356.3 V72.06 V (18.01%)41615.4 WDrop High
95 mm²232 A181 A32.19 V (8.05%)367.8 V53.1 V (13.27%)30663.9 WDrop High
120 mm²269 A210 A25.48 V (6.37%)374.5 V42.03 V (10.51%)24275.6 WDrop High
150 mm²309 A241 A20.39 V (5.1%)379.6 V33.63 V (8.41%)19420.5 WDrop High
185 mm²353 A275 A16.53 V (4.13%)383.5 V27.27 V (6.82%)15746.4 WDrop High
240 mm²415 A324 A12.74 V (3.19%)387.3 V21.02 V (5.25%)12137.8 WDrop High
300 mm²477 A372 A10.19 V (2.55%)389.8 V16.81 V (4.2%)9710.2 WDrop High
400 mm²570 A445 A7.64 V (1.91%)392.4 V12.61 V (3.15%)7282.7 W✓ OK (≤3%)

FAQ — Kabelarea för 550 Ampere vid 150 Meter (400V)

Vilken kabelarea krävs för 550A vid 150 meter (400V)?

För 550 Ampere över 150 meter vid 400V rekommenderas 400 mm² kopparkabel för att hålla spänningsfallet under 3% (7.64V / 1.91%).

Hur stor effekt motsvarar 550A vid 400V?

Det motsvarar 381.05 kW med en rekommenderad säkring på 600A.