Kabelarea för 550 Ampere vid 250 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 550 A över 250 m vid 400V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 6.37V (1.59%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 21.02V (5.25%)
Voltage at Load393.6 VLine Loss: 6068.9 W
Max Power & Breaker381.05 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3397.71 V (849.43%)0.0 V5604.63 V (1401.16%)3236750.0 WDrop High
2.5 mm²24 A18 A2038.62 V (509.66%)0.0 V3362.78 V (840.69%)1942050.0 WDrop High
4 mm²32 A25 A1274.14 V (318.53%)0.0 V2101.74 V (525.43%)1213781.2 WDrop High
6 mm²41 A32 A849.43 V (212.36%)0.0 V1401.16 V (350.29%)809187.5 WDrop High
10 mm²57 A44 A509.66 V (127.41%)0.0 V840.69 V (210.17%)485512.5 WDrop High
16 mm²76 A59 A318.53 V (79.63%)81.5 V525.43 V (131.36%)303445.3 WDrop High
25 mm²101 A78 A203.86 V (50.97%)196.1 V336.28 V (84.07%)194205.0 WDrop High
35 mm²125 A97 A145.62 V (36.4%)254.4 V240.2 V (60.05%)138717.9 WDrop High
50 mm²151 A118 A101.93 V (25.48%)298.1 V168.14 V (42.03%)97102.5 WDrop High
70 mm²192 A150 A72.81 V (18.2%)327.2 V120.1 V (30.02%)69358.9 WDrop High
95 mm²232 A181 A53.65 V (13.41%)346.4 V88.49 V (22.12%)51106.6 WDrop High
120 mm²269 A210 A42.47 V (10.62%)357.5 V70.06 V (17.51%)40459.4 WDrop High
150 mm²309 A241 A33.98 V (8.49%)366.0 V56.05 V (14.01%)32367.5 WDrop High
185 mm²353 A275 A27.55 V (6.89%)372.5 V45.44 V (11.36%)26243.9 WDrop High
240 mm²415 A324 A21.24 V (5.31%)378.8 V35.03 V (8.76%)20229.7 WDrop High
300 mm²477 A372 A16.99 V (4.25%)383.0 V28.02 V (7.01%)16183.8 WDrop High
400 mm²570 A445 A12.74 V (3.19%)387.3 V21.02 V (5.25%)12137.8 W~ ≤5%

FAQ — Kabelarea för 550 Ampere vid 250 Meter (400V)

Vilken kabelarea krävs för 550A vid 250 meter (400V)?

För 550 Ampere över 250 meter vid 400V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (6.37V / 1.59%).

Hur stor effekt motsvarar 550A vid 400V?

Det motsvarar 381.05 kW med en rekommenderad säkring på 600A.