Kabelarea för 60 Ampere vid 10 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 60 A över 10 m vid 230V.
Copper Cable (≤3% Drop)16 mm²Drop: 1.6V (0.7%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 1.69V (0.74%)
Voltage at Load228.4 VLine Loss: 96.3 W
Max Power & Breaker13.8 kW60A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 60A at 10m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 17.12 V (7.44%) | 212.9 V | 28.24 V (12.28%) | 1027.2 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 10.27 V (4.47%) | 219.7 V | 16.94 V (7.37%) | 616.3 W | Drop High |
| 4 mm² | 32 A | 25 A | 6.42 V (2.79%) | 223.6 V | 10.59 V (4.6%) | 385.2 W | Drop High |
| 6 mm² | 41 A | 32 A | 4.28 V (1.86%) | 225.7 V | 7.06 V (3.07%) | 256.8 W | Drop High |
| 10 mm² | 57 A | 44 A | 2.57 V (1.12%) | 227.4 V | 4.24 V (1.84%) | 154.1 W | Drop High |
| 16 mm² | 76 A | 59 A | 1.6 V (0.7%) | 228.4 V | 2.65 V (1.15%) | 96.3 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 1.03 V (0.45%) | 229.0 V | 1.69 V (0.74%) | 61.6 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 0.73 V (0.32%) | 229.3 V | 1.21 V (0.53%) | 44.0 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.51 V (0.22%) | 229.5 V | 0.85 V (0.37%) | 30.8 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.37 V (0.16%) | 229.6 V | 0.61 V (0.26%) | 22.0 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.27 V (0.12%) | 229.7 V | 0.45 V (0.19%) | 16.2 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.21 V (0.09%) | 229.8 V | 0.35 V (0.15%) | 12.8 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.17 V (0.07%) | 229.8 V | 0.28 V (0.12%) | 10.3 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.14 V (0.06%) | 229.9 V | 0.23 V (0.1%) | 8.3 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.11 V (0.05%) | 229.9 V | 0.18 V (0.08%) | 6.4 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.09 V (0.04%) | 229.9 V | 0.14 V (0.06%) | 5.1 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.06 V (0.03%) | 229.9 V | 0.11 V (0.05%) | 3.9 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 60 Ampere vid 10 Meter (230V)
Vilken kabelarea krävs för 60A vid 10 meter (230V)?
För 60 Ampere över 10 meter vid 230V rekommenderas 16 mm² kopparkabel för att hålla spänningsfallet under 3% (1.6V / 0.7%).
Hur stor effekt motsvarar 60A vid 230V?
Det motsvarar 13.8 kW med en rekommenderad säkring på 60A.
Related Lengths & Currents (230V)
60A · 5m (230V)60A · 15m (230V)60A · 20m (230V)60A · 25m (230V)60A · 30m (230V)60A · 35m (230V)60A · 40m (230V)60A · 45m (230V)60A · 50m (230V)60A · 60m (230V)60A · 70m (230V)10A · 10m (230V)16A · 10m (230V)20A · 10m (230V)25A · 10m (230V)32A · 10m (230V)40A · 10m (230V)50A · 10m (230V)63A · 10m (230V)80A · 10m (230V)100A · 10m (230V)125A · 10m (230V)160A · 10m (230V)200A · 10m (230V)