⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 60 Ampere vid 40 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 60 A över 40 m vid 230V.

Copper Cable (≤3% Drop)16 mm²Drop: 6.42V (2.79%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 6.78V (2.95%)
Voltage at Load223.6 VLine Loss: 385.2 W
Max Power & Breaker13.8 kW60A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 60A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A68.48 V (29.77%)161.5 V112.96 V (49.11%)4108.8 WDrop High
2.5 mm²24 A18 A41.09 V (17.86%)188.9 V67.78 V (29.47%)2465.3 WDrop High
4 mm²32 A25 A25.68 V (11.17%)204.3 V42.36 V (18.42%)1540.8 WDrop High
6 mm²41 A32 A17.12 V (7.44%)212.9 V28.24 V (12.28%)1027.2 WDrop High
10 mm²57 A44 A10.27 V (4.47%)219.7 V16.94 V (7.37%)616.3 WDrop High
16 mm²76 A59 A6.42 V (2.79%)223.6 V10.59 V (4.6%)385.2 W✓ OK (≤3%)
25 mm²101 A78 A4.11 V (1.79%)225.9 V6.78 V (2.95%)246.5 W✓ OK (≤3%)
35 mm²125 A97 A2.93 V (1.28%)227.1 V4.84 V (2.1%)176.1 W✓ OK (≤3%)
50 mm²151 A118 A2.05 V (0.89%)227.9 V3.39 V (1.47%)123.3 W✓ OK (≤3%)
70 mm²192 A150 A1.47 V (0.64%)228.5 V2.42 V (1.05%)88.0 W✓ OK (≤3%)
95 mm²232 A181 A1.08 V (0.47%)228.9 V1.78 V (0.78%)64.9 W✓ OK (≤3%)
120 mm²269 A210 A0.86 V (0.37%)229.1 V1.41 V (0.61%)51.4 W✓ OK (≤3%)
150 mm²309 A241 A0.68 V (0.3%)229.3 V1.13 V (0.49%)41.1 W✓ OK (≤3%)
185 mm²353 A275 A0.56 V (0.24%)229.4 V0.92 V (0.4%)33.3 W✓ OK (≤3%)
240 mm²415 A324 A0.43 V (0.19%)229.6 V0.71 V (0.31%)25.7 W✓ OK (≤3%)
300 mm²477 A372 A0.34 V (0.15%)229.7 V0.56 V (0.25%)20.5 W✓ OK (≤3%)
400 mm²570 A445 A0.26 V (0.11%)229.7 V0.42 V (0.18%)15.4 W✓ OK (≤3%)

FAQ — Kabelarea för 60 Ampere vid 40 Meter (230V)

Vilken kabelarea krävs för 60A vid 40 meter (230V)?

För 60 Ampere över 40 meter vid 230V rekommenderas 16 mm² kopparkabel för att hålla spänningsfallet under 3% (6.42V / 2.79%).

Hur stor effekt motsvarar 60A vid 230V?

Det motsvarar 13.8 kW med en rekommenderad säkring på 60A.