Kabelarea för 60 Ampere vid 20 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 60 A över 20 m vid 230V.
Copper Cable (≤3% Drop)16 mm²Drop: 3.21V (1.4%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 3.39V (1.47%)
Voltage at Load226.8 VLine Loss: 192.6 W
Max Power & Breaker13.8 kW60A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 60A at 20m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 34.24 V (14.89%) | 195.8 V | 56.48 V (24.56%) | 2054.4 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 20.54 V (8.93%) | 209.5 V | 33.89 V (14.73%) | 1232.6 W | Drop High |
| 4 mm² | 32 A | 25 A | 12.84 V (5.58%) | 217.2 V | 21.18 V (9.21%) | 770.4 W | Drop High |
| 6 mm² | 41 A | 32 A | 8.56 V (3.72%) | 221.4 V | 14.12 V (6.14%) | 513.6 W | Drop High |
| 10 mm² | 57 A | 44 A | 5.14 V (2.23%) | 224.9 V | 8.47 V (3.68%) | 308.2 W | Drop High |
| 16 mm² | 76 A | 59 A | 3.21 V (1.4%) | 226.8 V | 5.29 V (2.3%) | 192.6 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 2.05 V (0.89%) | 227.9 V | 3.39 V (1.47%) | 123.3 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 1.47 V (0.64%) | 228.5 V | 2.42 V (1.05%) | 88.0 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 1.03 V (0.45%) | 229.0 V | 1.69 V (0.74%) | 61.6 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.73 V (0.32%) | 229.3 V | 1.21 V (0.53%) | 44.0 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.54 V (0.24%) | 229.5 V | 0.89 V (0.39%) | 32.4 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.43 V (0.19%) | 229.6 V | 0.71 V (0.31%) | 25.7 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.34 V (0.15%) | 229.7 V | 0.56 V (0.25%) | 20.5 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.28 V (0.12%) | 229.7 V | 0.46 V (0.2%) | 16.7 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.21 V (0.09%) | 229.8 V | 0.35 V (0.15%) | 12.8 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.17 V (0.07%) | 229.8 V | 0.28 V (0.12%) | 10.3 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.13 V (0.06%) | 229.9 V | 0.21 V (0.09%) | 7.7 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 60 Ampere vid 20 Meter (230V)
Vilken kabelarea krävs för 60A vid 20 meter (230V)?
För 60 Ampere över 20 meter vid 230V rekommenderas 16 mm² kopparkabel för att hålla spänningsfallet under 3% (3.21V / 1.4%).
Hur stor effekt motsvarar 60A vid 230V?
Det motsvarar 13.8 kW med en rekommenderad säkring på 60A.
Related Lengths & Currents (230V)
60A · 5m (230V)60A · 10m (230V)60A · 15m (230V)60A · 25m (230V)60A · 30m (230V)60A · 35m (230V)60A · 40m (230V)60A · 45m (230V)60A · 50m (230V)60A · 60m (230V)60A · 70m (230V)10A · 20m (230V)16A · 20m (230V)20A · 20m (230V)25A · 20m (230V)32A · 20m (230V)40A · 20m (230V)50A · 20m (230V)63A · 20m (230V)80A · 20m (230V)100A · 20m (230V)125A · 20m (230V)160A · 20m (230V)200A · 20m (230V)