Kabelarea för 60 Ampere vid 5 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 60 A över 5 m vid 230V.
Copper Cable (≤3% Drop)16 mm²Drop: 0.8V (0.35%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 0.85V (0.37%)
Voltage at Load229.2 VLine Loss: 48.1 W
Max Power & Breaker13.8 kW60A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 60A at 5m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 8.56 V (3.72%) | 221.4 V | 14.12 V (6.14%) | 513.6 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 5.14 V (2.23%) | 224.9 V | 8.47 V (3.68%) | 308.2 W | Drop High |
| 4 mm² | 32 A | 25 A | 3.21 V (1.4%) | 226.8 V | 5.29 V (2.3%) | 192.6 W | Drop High |
| 6 mm² | 41 A | 32 A | 2.14 V (0.93%) | 227.9 V | 3.53 V (1.53%) | 128.4 W | Drop High |
| 10 mm² | 57 A | 44 A | 1.28 V (0.56%) | 228.7 V | 2.12 V (0.92%) | 77.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 0.8 V (0.35%) | 229.2 V | 1.32 V (0.58%) | 48.1 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 0.51 V (0.22%) | 229.5 V | 0.85 V (0.37%) | 30.8 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 0.37 V (0.16%) | 229.6 V | 0.61 V (0.26%) | 22.0 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.26 V (0.11%) | 229.7 V | 0.42 V (0.18%) | 15.4 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.18 V (0.08%) | 229.8 V | 0.3 V (0.13%) | 11.0 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.14 V (0.06%) | 229.9 V | 0.22 V (0.1%) | 8.1 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.11 V (0.05%) | 229.9 V | 0.18 V (0.08%) | 6.4 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.09 V (0.04%) | 229.9 V | 0.14 V (0.06%) | 5.1 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.07 V (0.03%) | 229.9 V | 0.11 V (0.05%) | 4.2 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.05 V (0.02%) | 229.9 V | 0.09 V (0.04%) | 3.2 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.04 V (0.02%) | 230.0 V | 0.07 V (0.03%) | 2.6 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.03 V (0.01%) | 230.0 V | 0.05 V (0.02%) | 1.9 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 60 Ampere vid 5 Meter (230V)
Vilken kabelarea krävs för 60A vid 5 meter (230V)?
För 60 Ampere över 5 meter vid 230V rekommenderas 16 mm² kopparkabel för att hålla spänningsfallet under 3% (0.8V / 0.35%).
Hur stor effekt motsvarar 60A vid 230V?
Det motsvarar 13.8 kW med en rekommenderad säkring på 60A.
Related Lengths & Currents (230V)
60A · 10m (230V)60A · 15m (230V)60A · 20m (230V)60A · 25m (230V)60A · 30m (230V)60A · 35m (230V)60A · 40m (230V)60A · 45m (230V)60A · 50m (230V)60A · 60m (230V)60A · 70m (230V)10A · 5m (230V)16A · 5m (230V)20A · 5m (230V)25A · 5m (230V)32A · 5m (230V)40A · 5m (230V)50A · 5m (230V)63A · 5m (230V)80A · 5m (230V)100A · 5m (230V)125A · 5m (230V)160A · 5m (230V)200A · 5m (230V)