Kabelarea för 60 Ampere vid 90 Meter (400V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 60 A över 90 m vid 400V.
Copper Cable (≤3% Drop)25 mm²Drop: 8.01V (2.0%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 9.43V (2.36%)
Voltage at Load392.0 VLine Loss: 832.0 W
Max Power & Breaker41.57 kW60A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 60A at 90m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 133.44 V (33.36%) | 266.6 V | 220.11 V (55.03%) | 13867.2 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 80.06 V (20.02%) | 319.9 V | 132.07 V (33.02%) | 8320.3 W | Drop High |
| 4 mm² | 32 A | 25 A | 50.04 V (12.51%) | 350.0 V | 82.54 V (20.64%) | 5200.2 W | Drop High |
| 6 mm² | 41 A | 32 A | 33.36 V (8.34%) | 366.6 V | 55.03 V (13.76%) | 3466.8 W | Drop High |
| 10 mm² | 57 A | 44 A | 20.02 V (5.0%) | 380.0 V | 33.02 V (8.25%) | 2080.1 W | Drop High |
| 16 mm² | 76 A | 59 A | 12.51 V (3.13%) | 387.5 V | 20.64 V (5.16%) | 1300.0 W | ~ ≤5% |
| 25 mm² | 101 A | 78 A | 8.01 V (2.0%) | 392.0 V | 13.21 V (3.3%) | 832.0 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 5.72 V (1.43%) | 394.3 V | 9.43 V (2.36%) | 594.3 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 4.0 V (1.0%) | 396.0 V | 6.6 V (1.65%) | 416.0 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 2.86 V (0.71%) | 397.1 V | 4.72 V (1.18%) | 297.2 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 2.11 V (0.53%) | 397.9 V | 3.48 V (0.87%) | 219.0 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 1.67 V (0.42%) | 398.3 V | 2.75 V (0.69%) | 173.3 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 1.33 V (0.33%) | 398.7 V | 2.2 V (0.55%) | 138.7 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 1.08 V (0.27%) | 398.9 V | 1.78 V (0.45%) | 112.4 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.83 V (0.21%) | 399.2 V | 1.38 V (0.34%) | 86.7 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.67 V (0.17%) | 399.3 V | 1.1 V (0.28%) | 69.3 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.5 V (0.13%) | 399.5 V | 0.83 V (0.21%) | 52.0 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 60 Ampere vid 90 Meter (400V)
Vilken kabelarea krävs för 60A vid 90 meter (400V)?
För 60 Ampere över 90 meter vid 400V rekommenderas 25 mm² kopparkabel för att hålla spänningsfallet under 3% (8.01V / 2.0%).
Hur stor effekt motsvarar 60A vid 400V?
Det motsvarar 41.57 kW med en rekommenderad säkring på 60A.
Related Lengths & Currents (400V)
60A · 5m (400V)60A · 10m (400V)60A · 15m (400V)60A · 20m (400V)60A · 25m (400V)60A · 30m (400V)60A · 35m (400V)60A · 40m (400V)60A · 45m (400V)60A · 50m (400V)60A · 60m (400V)60A · 70m (400V)10A · 90m (400V)16A · 90m (400V)20A · 90m (400V)25A · 90m (400V)32A · 90m (400V)40A · 90m (400V)50A · 90m (400V)63A · 90m (400V)80A · 90m (400V)100A · 90m (400V)125A · 90m (400V)160A · 90m (400V)200A · 90m (400V)