Kabelarea för 750 Ampere vid 175 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 750 A över 175 m vid 400V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 6.08V (1.52%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 20.06V (5.02%)
Voltage at Load393.9 VLine Loss: 7899.6 W
Max Power & Breaker519.62 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 750A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3243.27 V (810.82%)0.0 V5349.87 V (1337.47%)4213125.0 WDrop High
2.5 mm²24 A18 A1945.96 V (486.49%)0.0 V3209.92 V (802.48%)2527875.0 WDrop High
4 mm²32 A25 A1216.22 V (304.06%)0.0 V2006.2 V (501.55%)1579921.9 WDrop High
6 mm²41 A32 A810.82 V (202.7%)0.0 V1337.47 V (334.37%)1053281.2 WDrop High
10 mm²57 A44 A486.49 V (121.62%)0.0 V802.48 V (200.62%)631968.7 WDrop High
16 mm²76 A59 A304.06 V (76.01%)95.9 V501.55 V (125.39%)394980.5 WDrop High
25 mm²101 A78 A194.6 V (48.65%)205.4 V320.99 V (80.25%)252787.5 WDrop High
35 mm²125 A97 A139.0 V (34.75%)261.0 V229.28 V (57.32%)180562.5 WDrop High
50 mm²151 A118 A97.3 V (24.32%)302.7 V160.5 V (40.12%)126393.7 WDrop High
70 mm²192 A150 A69.5 V (17.37%)330.5 V114.64 V (28.66%)90281.2 WDrop High
95 mm²232 A181 A51.21 V (12.8%)348.8 V84.47 V (21.12%)66523.0 WDrop High
120 mm²269 A210 A40.54 V (10.14%)359.5 V66.87 V (16.72%)52664.1 WDrop High
150 mm²309 A241 A32.43 V (8.11%)367.6 V53.5 V (13.37%)42131.2 WDrop High
185 mm²353 A275 A26.3 V (6.57%)373.7 V43.38 V (10.84%)34160.5 WDrop High
240 mm²415 A324 A20.27 V (5.07%)379.7 V33.44 V (8.36%)26332.0 WDrop High
300 mm²477 A372 A16.22 V (4.05%)383.8 V26.75 V (6.69%)21065.6 WDrop High
400 mm²570 A445 A12.16 V (3.04%)387.8 V20.06 V (5.02%)15799.2 WDrop High

FAQ — Kabelarea för 750 Ampere vid 175 Meter (400V)

Vilken kabelarea krävs för 750A vid 175 meter (400V)?

För 750 Ampere över 175 meter vid 400V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (6.08V / 1.52%).

Hur stor effekt motsvarar 750A vid 400V?

Det motsvarar 519.62 kW med en rekommenderad säkring på 800A.