⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 800 Ampere vid 120 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 800 A över 120 m vid 230V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 5.13V (2.23%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 16.94V (7.37%)
Voltage at Load224.9 VLine Loss: 4108.8 W
Max Power & Breaker184.0 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 800A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2739.2 V (1190.96%)0.0 V4518.4 V (1964.52%)2191360.0 WDrop High
2.5 mm²24 A18 A1643.52 V (714.57%)0.0 V2711.04 V (1178.71%)1314816.0 WDrop High
4 mm²32 A25 A1027.2 V (446.61%)0.0 V1694.4 V (736.7%)821760.0 WDrop High
6 mm²41 A32 A684.8 V (297.74%)0.0 V1129.6 V (491.13%)547840.0 WDrop High
10 mm²57 A44 A410.88 V (178.64%)0.0 V677.76 V (294.68%)328704.0 WDrop High
16 mm²76 A59 A256.8 V (111.65%)0.0 V423.6 V (184.17%)205440.0 WDrop High
25 mm²101 A78 A164.35 V (71.46%)65.6 V271.1 V (117.87%)131481.6 WDrop High
35 mm²125 A97 A117.39 V (51.04%)112.6 V193.65 V (84.19%)93915.4 WDrop High
50 mm²151 A118 A82.18 V (35.73%)147.8 V135.55 V (58.94%)65740.8 WDrop High
70 mm²192 A150 A58.7 V (25.52%)171.3 V96.82 V (42.1%)46957.7 WDrop High
95 mm²232 A181 A43.25 V (18.8%)186.7 V71.34 V (31.02%)34600.4 WDrop High
120 mm²269 A210 A34.24 V (14.89%)195.8 V56.48 V (24.56%)27392.0 WDrop High
150 mm²309 A241 A27.39 V (11.91%)202.6 V45.18 V (19.65%)21913.6 WDrop High
185 mm²353 A275 A22.21 V (9.66%)207.8 V36.64 V (15.93%)17767.8 WDrop High
240 mm²415 A324 A17.12 V (7.44%)212.9 V28.24 V (12.28%)13696.0 WDrop High
300 mm²477 A372 A13.7 V (5.95%)216.3 V22.59 V (9.82%)10956.8 WDrop High
400 mm²570 A445 A10.27 V (4.47%)219.7 V16.94 V (7.37%)8217.6 WDrop High

FAQ — Kabelarea för 800 Ampere vid 120 Meter (230V)

Vilken kabelarea krävs för 800A vid 120 meter (230V)?

För 800 Ampere över 120 meter vid 230V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (5.13V / 2.23%).

Hur stor effekt motsvarar 800A vid 230V?

Det motsvarar 184.0 kW med en rekommenderad säkring på 800A.