Kabelarea för 800 Ampere vid 350 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 800 A över 350 m vid 230V.

Copper Cable (≤3% Drop)5× 400 mm²Drop: 5.99V (2.61%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 49.42V (21.49%)
Voltage at Load224.0 VLine Loss: 4793.6 W
Max Power & Breaker184.0 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 800A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A7989.33 V (3473.62%)0.0 V13178.67 V (5729.86%)6391466.7 WDrop High
2.5 mm²24 A18 A4793.6 V (2084.17%)0.0 V7907.2 V (3437.91%)3834880.0 WDrop High
4 mm²32 A25 A2996.0 V (1302.61%)0.0 V4942.0 V (2148.7%)2396800.0 WDrop High
6 mm²41 A32 A1997.33 V (868.41%)0.0 V3294.67 V (1432.46%)1597866.7 WDrop High
10 mm²57 A44 A1198.4 V (521.04%)0.0 V1976.8 V (859.48%)958720.0 WDrop High
16 mm²76 A59 A749.0 V (325.65%)0.0 V1235.5 V (537.17%)599200.0 WDrop High
25 mm²101 A78 A479.36 V (208.42%)0.0 V790.72 V (343.79%)383488.0 WDrop High
35 mm²125 A97 A342.4 V (148.87%)0.0 V564.8 V (245.57%)273920.0 WDrop High
50 mm²151 A118 A239.68 V (104.21%)0.0 V395.36 V (171.9%)191744.0 WDrop High
70 mm²192 A150 A171.2 V (74.43%)58.8 V282.4 V (122.78%)136960.0 WDrop High
95 mm²232 A181 A126.15 V (54.85%)103.9 V208.08 V (90.47%)100917.9 WDrop High
120 mm²269 A210 A99.87 V (43.42%)130.1 V164.73 V (71.62%)79893.3 WDrop High
150 mm²309 A241 A79.89 V (34.74%)150.1 V131.79 V (57.3%)63914.7 WDrop High
185 mm²353 A275 A64.78 V (28.16%)165.2 V106.85 V (46.46%)51822.7 WDrop High
240 mm²415 A324 A49.93 V (21.71%)180.1 V82.37 V (35.81%)39946.7 WDrop High
300 mm²477 A372 A39.95 V (17.37%)190.1 V65.89 V (28.65%)31957.3 WDrop High
400 mm²570 A445 A29.96 V (13.03%)200.0 V49.42 V (21.49%)23968.0 WDrop High

FAQ — Kabelarea för 800 Ampere vid 350 Meter (230V)

Vilken kabelarea krävs för 800A vid 350 meter (230V)?

För 800 Ampere över 350 meter vid 230V rekommenderas 5× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (5.99V / 2.61%).

Hur stor effekt motsvarar 800A vid 230V?

Det motsvarar 184.0 kW med en rekommenderad säkring på 800A.