Kabelarea för 800 Ampere vid 90 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 800 A över 90 m vid 400V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 3.33V (0.83%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 11.01V (2.75%)
Voltage at Load396.7 VLine Loss: 4622.4 W
Max Power & Breaker554.26 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 800A at 90m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1779.16 V (444.79%)0.0 V2934.79 V (733.7%)2465280.0 WDrop High
2.5 mm²24 A18 A1067.5 V (266.87%)0.0 V1760.87 V (440.22%)1479168.0 WDrop High
4 mm²32 A25 A667.19 V (166.8%)0.0 V1100.55 V (275.14%)924480.0 WDrop High
6 mm²41 A32 A444.79 V (111.2%)0.0 V733.7 V (183.42%)616320.0 WDrop High
10 mm²57 A44 A266.87 V (66.72%)133.1 V440.22 V (110.05%)369792.0 WDrop High
16 mm²76 A59 A166.8 V (41.7%)233.2 V275.14 V (68.78%)231120.0 WDrop High
25 mm²101 A78 A106.75 V (26.69%)293.3 V176.09 V (44.02%)147916.8 WDrop High
35 mm²125 A97 A76.25 V (19.06%)323.8 V125.78 V (31.44%)105654.9 WDrop High
50 mm²151 A118 A53.37 V (13.34%)346.6 V88.04 V (22.01%)73958.4 WDrop High
70 mm²192 A150 A38.12 V (9.53%)361.9 V62.89 V (15.72%)52827.4 WDrop High
95 mm²232 A181 A28.09 V (7.02%)371.9 V46.34 V (11.58%)38925.5 WDrop High
120 mm²269 A210 A22.24 V (5.56%)377.8 V36.68 V (9.17%)30816.0 WDrop High
150 mm²309 A241 A17.79 V (4.45%)382.2 V29.35 V (7.34%)24652.8 WDrop High
185 mm²353 A275 A14.43 V (3.61%)385.6 V23.8 V (5.95%)19988.8 WDrop High
240 mm²415 A324 A11.12 V (2.78%)388.9 V18.34 V (4.59%)15408.0 WDrop High
300 mm²477 A372 A8.9 V (2.22%)391.1 V14.67 V (3.67%)12326.4 WDrop High
400 mm²570 A445 A6.67 V (1.67%)393.3 V11.01 V (2.75%)9244.8 WDrop High

FAQ — Kabelarea för 800 Ampere vid 90 Meter (400V)

Vilken kabelarea krävs för 800A vid 90 meter (400V)?

För 800 Ampere över 90 meter vid 400V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (3.33V / 0.83%).

Hur stor effekt motsvarar 800A vid 400V?

Det motsvarar 554.26 kW med en rekommenderad säkring på 800A.