Kabelarea för 90 Ampere vid 120 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 90 A över 120 m vid 230V.

Copper Cable (≤3% Drop)70 mm²Drop: 6.6V (2.87%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 6.35V (2.76%)
Voltage at Load223.4 VLine Loss: 594.3 W
Max Power & Breaker20.7 kW90A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 90A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A308.16 V (133.98%)0.0 V508.32 V (221.01%)27734.4 WDrop High
2.5 mm²24 A18 A184.9 V (80.39%)45.1 V304.99 V (132.61%)16640.6 WDrop High
4 mm²32 A25 A115.56 V (50.24%)114.4 V190.62 V (82.88%)10400.4 WDrop High
6 mm²41 A32 A77.04 V (33.5%)153.0 V127.08 V (55.25%)6933.6 WDrop High
10 mm²57 A44 A46.22 V (20.1%)183.8 V76.25 V (33.15%)4160.2 WDrop High
16 mm²76 A59 A28.89 V (12.56%)201.1 V47.65 V (20.72%)2600.1 WDrop High
25 mm²101 A78 A18.49 V (8.04%)211.5 V30.5 V (13.26%)1664.1 WDrop High
35 mm²125 A97 A13.21 V (5.74%)216.8 V21.79 V (9.47%)1188.6 WDrop High
50 mm²151 A118 A9.24 V (4.02%)220.8 V15.25 V (6.63%)832.0 W~ ≤5%
70 mm²192 A150 A6.6 V (2.87%)223.4 V10.89 V (4.74%)594.3 W✓ OK (≤3%)
95 mm²232 A181 A4.87 V (2.12%)225.1 V8.03 V (3.49%)437.9 W✓ OK (≤3%)
120 mm²269 A210 A3.85 V (1.67%)226.1 V6.35 V (2.76%)346.7 W✓ OK (≤3%)
150 mm²309 A241 A3.08 V (1.34%)226.9 V5.08 V (2.21%)277.3 W✓ OK (≤3%)
185 mm²353 A275 A2.5 V (1.09%)227.5 V4.12 V (1.79%)224.9 W✓ OK (≤3%)
240 mm²415 A324 A1.93 V (0.84%)228.1 V3.18 V (1.38%)173.3 W✓ OK (≤3%)
300 mm²477 A372 A1.54 V (0.67%)228.5 V2.54 V (1.11%)138.7 W✓ OK (≤3%)
400 mm²570 A445 A1.16 V (0.5%)228.8 V1.91 V (0.83%)104.0 W✓ OK (≤3%)

FAQ — Kabelarea för 90 Ampere vid 120 Meter (230V)

Vilken kabelarea krävs för 90A vid 120 meter (230V)?

För 90 Ampere över 120 meter vid 230V rekommenderas 70 mm² kopparkabel för att hålla spänningsfallet under 3% (6.6V / 2.87%).

Hur stor effekt motsvarar 90A vid 230V?

Det motsvarar 20.7 kW med en rekommenderad säkring på 90A.