Kabelarea för 90 Ampere vid 500 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 90 A över 500 m vid 400V.

Copper Cable (≤3% Drop)150 mm²Drop: 11.12V (2.78%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 11.46V (2.87%)
Voltage at Load388.9 VLine Loss: 1733.4 W
Max Power & Breaker62.35 kW90A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 90A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1111.98 V (277.99%)0.0 V1834.24 V (458.56%)173340.0 WDrop High
2.5 mm²24 A18 A667.19 V (166.8%)0.0 V1100.55 V (275.14%)104004.0 WDrop High
4 mm²32 A25 A416.99 V (104.25%)0.0 V687.84 V (171.96%)65002.5 WDrop High
6 mm²41 A32 A277.99 V (69.5%)122.0 V458.56 V (114.64%)43335.0 WDrop High
10 mm²57 A44 A166.8 V (41.7%)233.2 V275.14 V (68.78%)26001.0 WDrop High
16 mm²76 A59 A104.25 V (26.06%)295.8 V171.96 V (42.99%)16250.6 WDrop High
25 mm²101 A78 A66.72 V (16.68%)333.3 V110.05 V (27.51%)10400.4 WDrop High
35 mm²125 A97 A47.66 V (11.91%)352.3 V78.61 V (19.65%)7428.9 WDrop High
50 mm²151 A118 A33.36 V (8.34%)366.6 V55.03 V (13.76%)5200.2 WDrop High
70 mm²192 A150 A23.83 V (5.96%)376.2 V39.31 V (9.83%)3714.4 WDrop High
95 mm²232 A181 A17.56 V (4.39%)382.4 V28.96 V (7.24%)2736.9 W~ ≤5%
120 mm²269 A210 A13.9 V (3.47%)386.1 V22.93 V (5.73%)2166.8 W~ ≤5%
150 mm²309 A241 A11.12 V (2.78%)388.9 V18.34 V (4.59%)1733.4 W✓ OK (≤3%)
185 mm²353 A275 A9.02 V (2.25%)391.0 V14.87 V (3.72%)1405.5 W✓ OK (≤3%)
240 mm²415 A324 A6.95 V (1.74%)393.1 V11.46 V (2.87%)1083.4 W✓ OK (≤3%)
300 mm²477 A372 A5.56 V (1.39%)394.4 V9.17 V (2.29%)866.7 W✓ OK (≤3%)
400 mm²570 A445 A4.17 V (1.04%)395.8 V6.88 V (1.72%)650.0 W✓ OK (≤3%)

FAQ — Kabelarea för 90 Ampere vid 500 Meter (400V)

Vilken kabelarea krävs för 90A vid 500 meter (400V)?

För 90 Ampere över 500 meter vid 400V rekommenderas 150 mm² kopparkabel för att hålla spänningsfallet under 3% (11.12V / 2.78%).

Hur stor effekt motsvarar 90A vid 400V?

Det motsvarar 62.35 kW med en rekommenderad säkring på 90A.