🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

10 Amp Wire Size at 275 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 10 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)4/0 AWG107.2 mm² · Drop: 2.79%
Aluminum Wire (≤3% Drop)350 kcmilDrop: 0.33V (2.78%)
Voltage at Load End11.7 VLoss: 0.33 V (3.3 W)
Power & Breaker (125%)0.12 kW13A Breaker Recommended

All AWG & kcmil Wire Gauges for 10 Amps at 275 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A17.25 V (143.73%)0.0 V28.45 V (237.09%)172.5 WDrop/Amp High
12 AWG3.31 mm²20 A10.84 V (90.32%)1.2 V17.88 V (148.99%)108.4 WDrop/Amp High
10 AWG5.26 mm²30 A6.82 V (56.84%)5.2 V11.25 V (93.75%)68.2 WDrop/Amp High
8 AWG8.37 mm²50 A4.29 V (35.72%)7.7 V7.07 V (58.92%)42.9 WDrop/Amp High
6 AWG13.3 mm²65 A2.7 V (22.48%)9.3 V4.45 V (37.08%)27.0 WDrop/Amp High
4 AWG21.15 mm²85 A1.7 V (14.14%)10.3 V2.8 V (23.32%)17.0 WDrop/Amp High
3 AWG26.67 mm²100 A1.35 V (11.21%)10.7 V2.22 V (18.49%)13.5 WDrop/Amp High
2 AWG33.62 mm²115 A1.07 V (8.89%)10.9 V1.76 V (14.67%)10.7 WDrop/Amp High
1 AWG42.41 mm²130 A0.85 V (7.05%)11.2 V1.4 V (11.63%)8.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A0.67 V (5.59%)11.3 V1.11 V (9.22%)6.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A0.53 V (4.43%)11.5 V0.88 V (7.31%)5.3 W~ ≤5%
3/0 AWG85.01 mm²200 A0.42 V (3.52%)11.6 V0.7 V (5.8%)4.2 W~ ≤5%
4/0 AWG107.2 mm²230 A0.33 V (2.79%)11.7 V0.55 V (4.6%)3.3 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.28 V (2.36%)11.7 V0.47 V (3.89%)2.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.24 V (1.97%)11.8 V0.39 V (3.24%)2.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.2 V (1.69%)11.8 V0.33 V (2.78%)2.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.18 V (1.47%)11.8 V0.29 V (2.43%)1.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.14 V (1.18%)11.9 V0.23 V (1.95%)1.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.12 V (0.98%)11.9 V0.19 V (1.62%)1.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.09 V (0.79%)11.9 V0.16 V (1.3%)0.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.07 V (0.59%)11.9 V0.12 V (0.97%)0.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 10 amps at 275 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 10A load over 275 feet one-way at 12V (DC), you need 4/0 AWG copper wire. This produces a voltage drop of 0.33V (2.79%) and delivers 11.7V at the load.

What size aluminum wire is required for 10 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 350 kcmil to maintain voltage drop at 0.33V (2.78%).

What breaker size is needed for a 10A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (10A × 1.25 = 12.5A), which corresponds to a standard 13A circuit breaker.