🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

10 Amp Wire Size at 125 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 10 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)1/0 AWG53.49 mm² · Drop: 2.54%
Aluminum Wire (≤3% Drop)3/0 AWGDrop: 0.32V (2.64%)
Voltage at Load End11.7 VLoss: 0.3 V (3.0 W)
Power & Breaker (125%)0.12 kW13A Breaker Recommended

All AWG & kcmil Wire Gauges for 10 Amps at 125 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A7.84 V (65.33%)4.2 V12.93 V (107.77%)78.4 WDrop/Amp High
12 AWG3.31 mm²20 A4.93 V (41.05%)7.1 V8.13 V (67.72%)49.3 WDrop/Amp High
10 AWG5.26 mm²30 A3.1 V (25.83%)8.9 V5.11 V (42.62%)31.0 WDrop/Amp High
8 AWG8.37 mm²50 A1.95 V (16.24%)10.1 V3.21 V (26.78%)19.5 WDrop/Amp High
6 AWG13.3 mm²65 A1.23 V (10.22%)10.8 V2.02 V (16.85%)12.3 WDrop/Amp High
4 AWG21.15 mm²85 A0.77 V (6.43%)11.2 V1.27 V (10.6%)7.7 WDrop/Amp High
3 AWG26.67 mm²100 A0.61 V (5.1%)11.4 V1.01 V (8.4%)6.1 WDrop/Amp High
2 AWG33.62 mm²115 A0.49 V (4.04%)11.5 V0.8 V (6.67%)4.9 W~ ≤5%
1 AWG42.41 mm²130 A0.38 V (3.2%)11.6 V0.63 V (5.29%)3.8 W~ ≤5%
1/0 AWG53.49 mm²150 A0.3 V (2.54%)11.7 V0.5 V (4.19%)3.0 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.24 V (2.02%)11.8 V0.4 V (3.32%)2.4 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.19 V (1.6%)11.8 V0.32 V (2.64%)1.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.15 V (1.27%)11.8 V0.25 V (2.09%)1.5 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.13 V (1.07%)11.9 V0.21 V (1.77%)1.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.11 V (0.89%)11.9 V0.18 V (1.47%)1.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.09 V (0.77%)11.9 V0.15 V (1.26%)0.9 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.08 V (0.67%)11.9 V0.13 V (1.11%)0.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.06 V (0.54%)11.9 V0.11 V (0.88%)0.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.05 V (0.45%)11.9 V0.09 V (0.74%)0.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.04 V (0.36%)12.0 V0.07 V (0.59%)0.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.03 V (0.27%)12.0 V0.05 V (0.44%)0.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 10 amps at 125 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 10A load over 125 feet one-way at 12V (DC), you need 1/0 AWG copper wire. This produces a voltage drop of 0.3V (2.54%) and delivers 11.7V at the load.

What size aluminum wire is required for 10 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 3/0 AWG to maintain voltage drop at 0.32V (2.64%).

What breaker size is needed for a 10A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (10A × 1.25 = 12.5A), which corresponds to a standard 13A circuit breaker.