⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

10 Amp Wire Size at 30 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 10 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)6 AWG13.3 mm² · Drop: 2.45%
Aluminum Wire (≤3% Drop)4 AWGDrop: 0.31V (2.54%)
Voltage at Load End11.7 VLoss: 0.29 V (2.9 W)
Power & Breaker (125%)0.12 kW13A Breaker Recommended

All AWG & kcmil Wire Gauges for 10 Amps at 30 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1.88 V (15.68%)10.1 V3.1 V (25.86%)18.8 WDrop/Amp High
12 AWG3.31 mm²20 A1.18 V (9.85%)10.8 V1.95 V (16.25%)11.8 WDrop/Amp High
10 AWG5.26 mm²30 A0.74 V (6.2%)11.3 V1.23 V (10.23%)7.4 WDrop/Amp High
8 AWG8.37 mm²50 A0.47 V (3.9%)11.5 V0.77 V (6.43%)4.7 W~ ≤5%
6 AWG13.3 mm²65 A0.29 V (2.45%)11.7 V0.49 V (4.04%)2.9 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A0.19 V (1.54%)11.8 V0.31 V (2.54%)1.9 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.15 V (1.22%)11.9 V0.24 V (2.02%)1.5 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.12 V (0.97%)11.9 V0.19 V (1.6%)1.2 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.09 V (0.77%)11.9 V0.15 V (1.27%)0.9 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.07 V (0.61%)11.9 V0.12 V (1.01%)0.7 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.06 V (0.48%)11.9 V0.1 V (0.8%)0.6 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.05 V (0.38%)12.0 V0.08 V (0.63%)0.5 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.04 V (0.3%)12.0 V0.06 V (0.5%)0.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.03 V (0.26%)12.0 V0.05 V (0.42%)0.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.03 V (0.21%)12.0 V0.04 V (0.35%)0.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.02 V (0.18%)12.0 V0.04 V (0.3%)0.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.02 V (0.16%)12.0 V0.03 V (0.27%)0.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.02 V (0.13%)12.0 V0.03 V (0.21%)0.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.01 V (0.11%)12.0 V0.02 V (0.18%)0.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.01 V (0.09%)12.0 V0.02 V (0.14%)0.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.01 V (0.06%)12.0 V0.01 V (0.11%)0.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 10 amps at 30 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 10A load over 30 feet one-way at 12V (DC), you need 6 AWG copper wire. This produces a voltage drop of 0.29V (2.45%) and delivers 11.7V at the load.

What size aluminum wire is required for 10 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 4 AWG to maintain voltage drop at 0.31V (2.54%).

What breaker size is needed for a 10A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (10A × 1.25 = 12.5A), which corresponds to a standard 13A circuit breaker.