🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

10 Amp Wire Size at 275 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 10 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)10 AWG5.26 mm² · Drop: 2.84%
Aluminum Wire (≤3% Drop)8 AWGDrop: 6.12V (2.94%)
Voltage at Load End202.1 VLoss: 5.91 V (102.3 W)
Power & Breaker (125%)3.6 kW13A Breaker Recommended

All AWG & kcmil Wire Gauges for 10 Amps at 275 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A14.94 V (7.18%)193.1 V24.64 V (11.85%)258.7 WDrop/Amp High
12 AWG3.31 mm²20 A9.39 V (4.51%)198.6 V15.48 V (7.44%)162.6 W~ ≤5%
10 AWG5.26 mm²30 A5.91 V (2.84%)202.1 V9.74 V (4.68%)102.3 W✓ PASS (≤3%)
8 AWG8.37 mm²50 A3.71 V (1.78%)204.3 V6.12 V (2.94%)64.3 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A2.34 V (1.12%)205.7 V3.85 V (1.85%)40.5 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A1.47 V (0.71%)206.5 V2.42 V (1.16%)25.4 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.16 V (0.56%)206.8 V1.92 V (0.92%)20.2 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.92 V (0.44%)207.1 V1.52 V (0.73%)16.0 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.73 V (0.35%)207.3 V1.21 V (0.58%)12.7 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.58 V (0.28%)207.4 V0.96 V (0.46%)10.1 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.46 V (0.22%)207.5 V0.76 V (0.37%)8.0 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.37 V (0.18%)207.6 V0.6 V (0.29%)6.3 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.29 V (0.14%)207.7 V0.48 V (0.23%)5.0 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.25 V (0.12%)207.8 V0.4 V (0.19%)4.2 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.2 V (0.1%)207.8 V0.34 V (0.16%)3.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.18 V (0.08%)207.8 V0.29 V (0.14%)3.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.15 V (0.07%)207.8 V0.25 V (0.12%)2.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.12 V (0.06%)207.9 V0.2 V (0.1%)2.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.1 V (0.05%)207.9 V0.17 V (0.08%)1.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.08 V (0.04%)207.9 V0.13 V (0.06%)1.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.06 V (0.03%)207.9 V0.1 V (0.05%)1.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 10 amps at 275 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 10A load over 275 feet one-way at 208V (3-Phase), you need 10 AWG copper wire. This produces a voltage drop of 5.91V (2.84%) and delivers 202.1V at the load.

What size aluminum wire is required for 10 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 8 AWG to maintain voltage drop at 6.12V (2.94%).

What breaker size is needed for a 10A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (10A × 1.25 = 12.5A), which corresponds to a standard 13A circuit breaker.