🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

1000 Amp Wire Size at 400 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 1000 A load over a 400 ft (121.9 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.93%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 14.71V (3.06%)
Voltage at Load End475.5 VLoss: 4.46 V (7723.8 W)
Power & Breaker (125%)831.38 kW1600A Breaker Recommended

All AWG & kcmil Wire Gauges for 1000 Amps at 400 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2172.63 V (452.63%)0.0 V3583.83 V (746.63%)3763107.7 WDrop/Amp High
12 AWG3.31 mm²20 A1365.28 V (284.43%)0.0 V2252.07 V (469.18%)2364732.3 WDrop/Amp High
10 AWG5.26 mm²30 A859.14 V (178.99%)0.0 V1417.18 V (295.25%)1488073.0 WDrop/Amp High
8 AWG8.37 mm²50 A539.91 V (112.48%)0.0 V890.6 V (185.54%)935157.0 WDrop/Amp High
6 AWG13.3 mm²65 A339.78 V (70.79%)140.2 V560.48 V (116.77%)588516.1 WDrop/Amp High
4 AWG21.15 mm²85 A213.67 V (44.51%)266.3 V352.45 V (73.43%)370083.4 WDrop/Amp High
3 AWG26.67 mm²100 A169.44 V (35.3%)310.6 V279.5 V (58.23%)293485.7 WDrop/Amp High
2 AWG33.62 mm²115 A134.42 V (28.0%)345.6 V221.72 V (46.19%)232815.7 WDrop/Amp High
1 AWG42.41 mm²130 A106.56 V (22.2%)373.4 V175.77 V (36.62%)184561.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A84.48 V (17.6%)395.5 V139.36 V (29.03%)146331.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A67.02 V (13.96%)413.0 V110.55 V (23.03%)116079.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A53.16 V (11.07%)426.8 V87.69 V (18.27%)92074.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A42.16 V (8.78%)437.8 V69.54 V (14.49%)73015.5 WDrop/Amp High
250 kcmil126.7 mm²255 A35.67 V (7.43%)444.3 V58.83 V (12.26%)61777.9 WDrop/Amp High
300 kcmil152.0 mm²285 A29.73 V (6.19%)450.3 V49.04 V (10.22%)51495.2 WDrop/Amp High
350 kcmil177.3 mm²310 A25.49 V (5.31%)454.5 V42.04 V (8.76%)44147.0 WDrop/Amp High
400 kcmil202.7 mm²335 A22.29 V (4.64%)457.7 V36.78 V (7.66%)38615.0 WDrop/Amp High
500 kcmil253.4 mm²380 A17.83 V (3.72%)462.2 V29.42 V (6.13%)30889.0 WDrop/Amp High
600 kcmil304.0 mm²420 A14.87 V (3.1%)465.1 V24.52 V (5.11%)25747.6 WDrop/Amp High
750 kcmil380.0 mm²475 A11.89 V (2.48%)468.1 V19.62 V (4.09%)20598.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A8.92 V (1.86%)471.1 V14.71 V (3.06%)15447.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 1000 amps at 400 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 1000A load over 400 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 4.46V (0.93%) and delivers 475.5V at the load.

What size aluminum wire is required for 1000 amps at 400 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 14.71V (3.06%).

What breaker size is needed for a 1000A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (1000A × 1.25 = 1250.0A), which corresponds to a standard 1600A circuit breaker.