🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 225 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)1/0 AWG53.49 mm² · Drop: 2.52%
Aluminum Wire (≤3% Drop)3/0 AWGDrop: 6.27V (2.61%)
Voltage at Load End234.0 VLoss: 6.04 V (664.0 W)
Power & Breaker (125%)26.4 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 225 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A155.23 V (64.68%)84.8 V256.05 V (106.69%)17075.1 WDrop/Amp High
12 AWG3.31 mm²20 A97.55 V (40.64%)142.5 V160.9 V (67.04%)10730.0 WDrop/Amp High
10 AWG5.26 mm²30 A61.38 V (25.58%)178.6 V101.25 V (42.19%)6752.1 WDrop/Amp High
8 AWG8.37 mm²50 A38.58 V (16.07%)201.4 V63.63 V (26.51%)4243.3 WDrop/Amp High
6 AWG13.3 mm²65 A24.28 V (10.12%)215.7 V40.04 V (16.69%)2670.4 WDrop/Amp High
4 AWG21.15 mm²85 A15.27 V (6.36%)224.7 V25.18 V (10.49%)1679.3 WDrop/Amp High
3 AWG26.67 mm²100 A12.11 V (5.04%)227.9 V19.97 V (8.32%)1331.7 WDrop/Amp High
2 AWG33.62 mm²115 A9.6 V (4.0%)230.4 V15.84 V (6.6%)1056.4 W~ ≤5%
1 AWG42.41 mm²130 A7.61 V (3.17%)232.4 V12.56 V (5.23%)837.4 W~ ≤5%
1/0 AWG53.49 mm²150 A6.04 V (2.52%)234.0 V9.96 V (4.15%)664.0 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A4.79 V (2.0%)235.2 V7.9 V (3.29%)526.7 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A3.8 V (1.58%)236.2 V6.27 V (2.61%)417.8 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A3.01 V (1.25%)237.0 V4.97 V (2.07%)331.3 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.55 V (1.06%)237.5 V4.2 V (1.75%)280.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.12 V (0.89%)237.9 V3.5 V (1.46%)233.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.82 V (0.76%)238.2 V3.0 V (1.25%)200.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.59 V (0.66%)238.4 V2.63 V (1.09%)175.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.27 V (0.53%)238.7 V2.1 V (0.88%)140.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.06 V (0.44%)238.9 V1.75 V (0.73%)116.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.85 V (0.35%)239.2 V1.4 V (0.58%)93.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.64 V (0.27%)239.4 V1.05 V (0.44%)70.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 225 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 225 feet one-way at 240V (1-Phase), you need 1/0 AWG copper wire. This produces a voltage drop of 6.04V (2.52%) and delivers 234.0V at the load.

What size aluminum wire is required for 110 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 3/0 AWG to maintain voltage drop at 6.27V (2.61%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.