🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 350 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)2/0 AWG67.43 mm² · Drop: 2.69%
Aluminum Wire (≤3% Drop)4/0 AWGDrop: 6.69V (2.79%)
Voltage at Load End233.5 VLoss: 6.45 V (1229.0 W)
Power & Breaker (125%)45.73 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 350 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A209.12 V (87.13%)30.9 V344.94 V (143.73%)39841.9 WDrop/Amp High
12 AWG3.31 mm²20 A131.41 V (54.75%)108.6 V216.76 V (90.32%)25036.6 WDrop/Amp High
10 AWG5.26 mm²30 A82.69 V (34.46%)157.3 V136.4 V (56.83%)15755.0 WDrop/Amp High
8 AWG8.37 mm²50 A51.97 V (21.65%)188.0 V85.72 V (35.72%)9901.0 WDrop/Amp High
6 AWG13.3 mm²65 A32.7 V (13.63%)207.3 V53.95 V (22.48%)6230.9 WDrop/Amp High
4 AWG21.15 mm²85 A20.57 V (8.57%)219.4 V33.92 V (14.13%)3918.3 WDrop/Amp High
3 AWG26.67 mm²100 A16.31 V (6.8%)223.7 V26.9 V (11.21%)3107.3 WDrop/Amp High
2 AWG33.62 mm²115 A12.94 V (5.39%)227.1 V21.34 V (8.89%)2464.9 WDrop/Amp High
1 AWG42.41 mm²130 A10.26 V (4.27%)229.7 V16.92 V (7.05%)1954.0 W~ ≤5%
1/0 AWG53.49 mm²150 A8.13 V (3.39%)231.9 V13.41 V (5.59%)1549.3 W~ ≤5%
2/0 AWG67.43 mm²175 A6.45 V (2.69%)233.5 V10.64 V (4.43%)1229.0 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A5.12 V (2.13%)234.9 V8.44 V (3.52%)974.8 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A4.06 V (1.69%)235.9 V6.69 V (2.79%)773.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A3.43 V (1.43%)236.6 V5.66 V (2.36%)654.1 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.86 V (1.19%)237.1 V4.72 V (1.97%)545.2 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.45 V (1.02%)237.5 V4.05 V (1.69%)467.4 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.15 V (0.89%)237.9 V3.54 V (1.47%)408.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.72 V (0.72%)238.3 V2.83 V (1.18%)327.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.43 V (0.6%)238.6 V2.36 V (0.98%)272.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.14 V (0.48%)238.9 V1.89 V (0.79%)218.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.86 V (0.36%)239.1 V1.42 V (0.59%)163.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 350 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 350 feet one-way at 240V (3-Phase), you need 2/0 AWG copper wire. This produces a voltage drop of 6.45V (2.69%) and delivers 233.5V at the load.

What size aluminum wire is required for 110 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 4/0 AWG to maintain voltage drop at 6.69V (2.79%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.