⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 600 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)250 kcmil126.7 mm² · Drop: 2.83%
Aluminum Wire (≤3% Drop)400 kcmilDrop: 7.01V (2.92%)
Voltage at Load End233.2 VLoss: 6.8 V (747.5 W)
Power & Breaker (125%)26.4 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 600 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A413.94 V (172.48%)0.0 V682.81 V (284.5%)45533.6 WDrop/Amp High
12 AWG3.31 mm²20 A260.12 V (108.38%)0.0 V429.08 V (178.78%)28613.3 WDrop/Amp High
10 AWG5.26 mm²30 A163.69 V (68.2%)76.3 V270.01 V (112.5%)18005.7 WDrop/Amp High
8 AWG8.37 mm²50 A102.87 V (42.86%)137.1 V169.68 V (70.7%)11315.4 WDrop/Amp High
6 AWG13.3 mm²65 A64.74 V (26.97%)175.3 V106.79 V (44.49%)7121.0 WDrop/Amp High
4 AWG21.15 mm²85 A40.71 V (16.96%)199.3 V67.15 V (27.98%)4478.0 WDrop/Amp High
3 AWG26.67 mm²100 A32.28 V (13.45%)207.7 V53.25 V (22.19%)3551.2 WDrop/Amp High
2 AWG33.62 mm²115 A25.61 V (10.67%)214.4 V42.24 V (17.6%)2817.1 WDrop/Amp High
1 AWG42.41 mm²130 A20.3 V (8.46%)219.7 V33.49 V (13.95%)2233.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A16.1 V (6.71%)223.9 V26.55 V (11.06%)1770.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A12.77 V (5.32%)227.2 V21.06 V (8.78%)1404.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A10.13 V (4.22%)229.9 V16.71 V (6.96%)1114.1 W~ ≤5%
4/0 AWG107.2 mm²230 A8.03 V (3.35%)232.0 V13.25 V (5.52%)883.5 W~ ≤5%
250 kcmil126.7 mm²255 A6.8 V (2.83%)233.2 V11.21 V (4.67%)747.5 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A5.66 V (2.36%)234.3 V9.34 V (3.89%)623.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A4.86 V (2.02%)235.1 V8.01 V (3.34%)534.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A4.25 V (1.77%)235.8 V7.01 V (2.92%)467.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A3.4 V (1.42%)236.6 V5.6 V (2.34%)373.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.83 V (1.18%)237.2 V4.67 V (1.95%)311.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.27 V (0.94%)237.7 V3.74 V (1.56%)249.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.7 V (0.71%)238.3 V2.8 V (1.17%)186.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 600 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 600 feet one-way at 240V (1-Phase), you need 250 kcmil copper wire. This produces a voltage drop of 6.8V (2.83%) and delivers 233.2V at the load.

What size aluminum wire is required for 110 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 400 kcmil to maintain voltage drop at 7.01V (2.92%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.