🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 75 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)600 kcmil304.0 mm² · Drop: 2.95%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.35V (2.92%)
Voltage at Load End11.6 VLoss: 0.35 V (38.9 W)
Power & Breaker (125%)1.32 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 75 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A51.74 V (431.19%)0.0 V85.35 V (711.26%)5691.7 WDrop/Amp High
12 AWG3.31 mm²20 A32.52 V (270.96%)0.0 V53.63 V (446.96%)3576.7 WDrop/Amp High
10 AWG5.26 mm²30 A20.46 V (170.51%)0.0 V33.75 V (281.26%)2250.7 WDrop/Amp High
8 AWG8.37 mm²50 A12.86 V (107.15%)0.0 V21.21 V (176.75%)1414.4 WDrop/Amp High
6 AWG13.3 mm²65 A8.09 V (67.43%)3.9 V13.35 V (111.23%)890.1 WDrop/Amp High
4 AWG21.15 mm²85 A5.09 V (42.41%)6.9 V8.39 V (69.95%)559.8 WDrop/Amp High
3 AWG26.67 mm²100 A4.04 V (33.63%)8.0 V6.66 V (55.47%)443.9 WDrop/Amp High
2 AWG33.62 mm²115 A3.2 V (26.68%)8.8 V5.28 V (44.0%)352.1 WDrop/Amp High
1 AWG42.41 mm²130 A2.54 V (21.15%)9.5 V4.19 V (34.88%)279.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A2.01 V (16.77%)10.0 V3.32 V (27.66%)221.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.6 V (13.3%)10.4 V2.63 V (21.94%)175.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.27 V (10.55%)10.7 V2.09 V (17.4%)139.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.0 V (8.37%)11.0 V1.66 V (13.8%)110.4 WDrop/Amp High
250 kcmil126.7 mm²255 A0.85 V (7.08%)11.2 V1.4 V (11.68%)93.4 WDrop/Amp High
300 kcmil152.0 mm²285 A0.71 V (5.9%)11.3 V1.17 V (9.73%)77.9 WDrop/Amp High
350 kcmil177.3 mm²310 A0.61 V (5.06%)11.4 V1.0 V (8.34%)66.8 WDrop/Amp High
400 kcmil202.7 mm²335 A0.53 V (4.42%)11.5 V0.88 V (7.3%)58.4 W~ ≤5%
500 kcmil253.4 mm²380 A0.42 V (3.54%)11.6 V0.7 V (5.84%)46.7 W~ ≤5%
600 kcmil304.0 mm²420 A0.35 V (2.95%)11.6 V0.58 V (4.87%)38.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.28 V (2.36%)11.7 V0.47 V (3.89%)31.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.21 V (1.77%)11.8 V0.35 V (2.92%)23.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 75 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 75 feet one-way at 12V (DC), you need 600 kcmil copper wire. This produces a voltage drop of 0.35V (2.95%) and delivers 11.6V at the load.

What size aluminum wire is required for 110 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.35V (2.92%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.