🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 20 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 20 ft (6.1 m) one-way run.

Copper Wire (≤3% Drop)3/0 AWG85.01 mm² · Drop: 2.81%
Aluminum Wire (≤3% Drop)300 kcmilDrop: 0.31V (2.6%)
Voltage at Load End11.7 VLoss: 0.34 V (37.1 W)
Power & Breaker (125%)1.32 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 20 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A13.8 V (114.98%)0.0 V22.76 V (189.67%)1517.8 WDrop/Amp High
12 AWG3.31 mm²20 A8.67 V (72.26%)3.3 V14.3 V (119.19%)953.8 WDrop/Amp High
10 AWG5.26 mm²30 A5.46 V (45.47%)6.5 V9.0 V (75.0%)600.2 WDrop/Amp High
8 AWG8.37 mm²50 A3.43 V (28.57%)8.6 V5.66 V (47.13%)377.2 WDrop/Amp High
6 AWG13.3 mm²65 A2.16 V (17.98%)9.8 V3.56 V (29.66%)237.4 WDrop/Amp High
4 AWG21.15 mm²85 A1.36 V (11.31%)10.6 V2.24 V (18.65%)149.3 WDrop/Amp High
3 AWG26.67 mm²100 A1.08 V (8.97%)10.9 V1.78 V (14.79%)118.4 WDrop/Amp High
2 AWG33.62 mm²115 A0.85 V (7.11%)11.1 V1.41 V (11.73%)93.9 WDrop/Amp High
1 AWG42.41 mm²130 A0.68 V (5.64%)11.3 V1.12 V (9.3%)74.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A0.54 V (4.47%)11.5 V0.89 V (7.38%)59.0 W~ ≤5%
2/0 AWG67.43 mm²175 A0.43 V (3.55%)11.6 V0.7 V (5.85%)46.8 W~ ≤5%
3/0 AWG85.01 mm²200 A0.34 V (2.81%)11.7 V0.56 V (4.64%)37.1 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.27 V (2.23%)11.7 V0.44 V (3.68%)29.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.23 V (1.89%)11.8 V0.37 V (3.11%)24.9 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.19 V (1.57%)11.8 V0.31 V (2.6%)20.8 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.16 V (1.35%)11.8 V0.27 V (2.23%)17.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.14 V (1.18%)11.9 V0.23 V (1.95%)15.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.11 V (0.94%)11.9 V0.19 V (1.56%)12.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.09 V (0.79%)11.9 V0.16 V (1.3%)10.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.08 V (0.63%)11.9 V0.12 V (1.04%)8.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.06 V (0.47%)11.9 V0.09 V (0.78%)6.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 20 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 20 feet one-way at 12V (DC), you need 3/0 AWG copper wire. This produces a voltage drop of 0.34V (2.81%) and delivers 11.7V at the load.

What size aluminum wire is required for 110 amps at 20 feet?

Using aluminum conductors (75°C rating), you should use 300 kcmil to maintain voltage drop at 0.31V (2.6%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.