⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 80 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 2.52%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.37V (3.11%)
Voltage at Load End11.7 VLoss: 0.3 V (33.2 W)
Power & Breaker (125%)1.32 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 80 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A55.19 V (459.94%)0.0 V91.04 V (758.68%)6071.1 WDrop/Amp High
12 AWG3.31 mm²20 A34.68 V (289.02%)0.0 V57.21 V (476.75%)3815.1 WDrop/Amp High
10 AWG5.26 mm²30 A21.83 V (181.88%)0.0 V36.0 V (300.01%)2400.8 WDrop/Amp High
8 AWG8.37 mm²50 A13.72 V (114.3%)0.0 V22.62 V (188.54%)1508.7 WDrop/Amp High
6 AWG13.3 mm²65 A8.63 V (71.93%)3.4 V14.24 V (118.65%)949.5 WDrop/Amp High
4 AWG21.15 mm²85 A5.43 V (45.23%)6.6 V8.95 V (74.61%)597.1 WDrop/Amp High
3 AWG26.67 mm²100 A4.3 V (35.87%)7.7 V7.1 V (59.17%)473.5 WDrop/Amp High
2 AWG33.62 mm²115 A3.41 V (28.46%)8.6 V5.63 V (46.94%)375.6 WDrop/Amp High
1 AWG42.41 mm²130 A2.71 V (22.56%)9.3 V4.47 V (37.21%)297.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A2.15 V (17.88%)9.9 V3.54 V (29.5%)236.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.7 V (14.19%)10.3 V2.81 V (23.4%)187.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.35 V (11.25%)10.6 V2.23 V (18.56%)148.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.07 V (8.92%)10.9 V1.77 V (14.72%)117.8 WDrop/Amp High
250 kcmil126.7 mm²255 A0.91 V (7.55%)11.1 V1.49 V (12.46%)99.7 WDrop/Amp High
300 kcmil152.0 mm²285 A0.76 V (6.29%)11.2 V1.25 V (10.38%)83.1 WDrop/Amp High
350 kcmil177.3 mm²310 A0.65 V (5.4%)11.4 V1.07 V (8.9%)71.2 WDrop/Amp High
400 kcmil202.7 mm²335 A0.57 V (4.72%)11.4 V0.93 V (7.79%)62.3 W~ ≤5%
500 kcmil253.4 mm²380 A0.45 V (3.78%)11.5 V0.75 V (6.23%)49.8 W~ ≤5%
600 kcmil304.0 mm²420 A0.38 V (3.15%)11.6 V0.62 V (5.19%)41.5 W~ ≤5%
750 kcmil380.0 mm²475 A0.3 V (2.52%)11.7 V0.5 V (4.15%)33.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.23 V (1.89%)11.8 V0.37 V (3.11%)24.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 80 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 80 feet one-way at 12V (DC), you need 750 kcmil copper wire. This produces a voltage drop of 0.3V (2.52%) and delivers 11.7V at the load.

What size aluminum wire is required for 110 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.37V (3.11%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.