🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

15 Amp Wire Size at 80 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 15 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)12 AWG3.31 mm² · Drop: 1.97%
Aluminum Wire (≤3% Drop)10 AWGDrop: 4.25V (2.04%)
Voltage at Load End203.9 VLoss: 4.1 V (106.4 W)
Power & Breaker (125%)5.4 kW20A Breaker Recommended

All AWG & kcmil Wire Gauges for 15 Amps at 80 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A6.52 V (3.13%)201.5 V10.75 V (5.17%)169.3 W~ ≤5%
12 AWG3.31 mm²20 A4.1 V (1.97%)203.9 V6.76 V (3.25%)106.4 W✓ PASS (≤3%)
10 AWG5.26 mm²30 A2.58 V (1.24%)205.4 V4.25 V (2.04%)67.0 W✓ PASS (≤3%)
8 AWG8.37 mm²50 A1.62 V (0.78%)206.4 V2.67 V (1.28%)42.1 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A1.02 V (0.49%)207.0 V1.68 V (0.81%)26.5 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A0.64 V (0.31%)207.4 V1.06 V (0.51%)16.7 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.51 V (0.24%)207.5 V0.84 V (0.4%)13.2 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.4 V (0.19%)207.6 V0.67 V (0.32%)10.5 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.32 V (0.15%)207.7 V0.53 V (0.25%)8.3 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.25 V (0.12%)207.7 V0.42 V (0.2%)6.6 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.2 V (0.1%)207.8 V0.33 V (0.16%)5.2 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.16 V (0.08%)207.8 V0.26 V (0.13%)4.1 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.13 V (0.06%)207.9 V0.21 V (0.1%)3.3 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.11 V (0.05%)207.9 V0.18 V (0.08%)2.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.09 V (0.04%)207.9 V0.15 V (0.07%)2.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.08 V (0.04%)207.9 V0.13 V (0.06%)2.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.07 V (0.03%)207.9 V0.11 V (0.05%)1.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.05 V (0.03%)207.9 V0.09 V (0.04%)1.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.04 V (0.02%)208.0 V0.07 V (0.04%)1.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.04 V (0.02%)208.0 V0.06 V (0.03%)0.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.03 V (0.01%)208.0 V0.04 V (0.02%)0.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 15 amps at 80 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 15A load over 80 feet one-way at 208V (3-Phase), you need 12 AWG copper wire. This produces a voltage drop of 4.1V (1.97%) and delivers 203.9V at the load.

What size aluminum wire is required for 15 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 10 AWG to maintain voltage drop at 4.25V (2.04%).

What breaker size is needed for a 15A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (15A × 1.25 = 18.8A), which corresponds to a standard 20A circuit breaker.