⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

175 Amp Wire Size at 200 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 175 A load over a 200 ft (61.0 m) one-way run.

Copper Wire (≤3% Drop)300 kcmil152.0 mm² · Drop: 2.5%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 2.97V (2.48%)
Voltage at Load End117.0 VLoss: 3.0 V (525.7 W)
Power & Breaker (125%)21.0 kW225A Breaker Recommended

All AWG & kcmil Wire Gauges for 175 Amps at 200 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A219.51 V (182.93%)0.0 V362.1 V (301.75%)38415.1 WDrop/Amp High
12 AWG3.31 mm²20 A137.94 V (114.95%)0.0 V227.54 V (189.62%)24140.0 WDrop/Amp High
10 AWG5.26 mm²30 A86.8 V (72.34%)33.2 V143.19 V (119.32%)15190.7 WDrop/Amp High
8 AWG8.37 mm²50 A54.55 V (45.46%)65.4 V89.98 V (74.99%)9546.4 WDrop/Amp High
6 AWG13.3 mm²65 A34.33 V (28.61%)85.7 V56.63 V (47.19%)6007.8 WDrop/Amp High
4 AWG21.15 mm²85 A21.59 V (17.99%)98.4 V35.61 V (29.68%)3777.9 WDrop/Amp High
3 AWG26.67 mm²100 A17.12 V (14.27%)102.9 V28.24 V (23.53%)2996.0 WDrop/Amp High
2 AWG33.62 mm²115 A13.58 V (11.32%)106.4 V22.4 V (18.67%)2376.7 WDrop/Amp High
1 AWG42.41 mm²130 A10.77 V (8.97%)109.2 V17.76 V (14.8%)1884.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A8.54 V (7.11%)111.5 V14.08 V (11.73%)1493.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A6.77 V (5.64%)113.2 V11.17 V (9.31%)1185.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A5.37 V (4.48%)114.6 V8.86 V (7.38%)939.9 W~ ≤5%
4/0 AWG107.2 mm²230 A4.26 V (3.55%)115.7 V7.03 V (5.85%)745.4 W~ ≤5%
250 kcmil126.7 mm²255 A3.6 V (3.0%)116.4 V5.94 V (4.95%)630.6 W~ ≤5%
300 kcmil152.0 mm²285 A3.0 V (2.5%)117.0 V4.96 V (4.13%)525.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.58 V (2.15%)117.4 V4.25 V (3.54%)450.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.25 V (1.88%)117.7 V3.72 V (3.1%)394.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.8 V (1.5%)118.2 V2.97 V (2.48%)315.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.5 V (1.25%)118.5 V2.48 V (2.06%)262.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.2 V (1.0%)118.8 V1.98 V (1.65%)210.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.9 V (0.75%)119.1 V1.49 V (1.24%)157.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 175 amps at 200 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 175A load over 200 feet one-way at 120V (1-Phase), you need 300 kcmil copper wire. This produces a voltage drop of 3.0V (2.5%) and delivers 117.0V at the load.

What size aluminum wire is required for 175 amps at 200 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 2.97V (2.48%).

What breaker size is needed for a 175A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (175A × 1.25 = 218.8A), which corresponds to a standard 225A circuit breaker.