⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

175 Amp Wire Size at 225 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 175 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)2/0 AWG67.43 mm² · Drop: 1.37%
Aluminum Wire (≤3% Drop)4/0 AWGDrop: 6.85V (1.43%)
Voltage at Load End473.4 VLoss: 6.6 V (1999.7 W)
Power & Breaker (125%)145.49 kW225A Breaker Recommended

All AWG & kcmil Wire Gauges for 175 Amps at 225 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A213.87 V (44.56%)266.1 V352.78 V (73.5%)64825.4 WDrop/Amp High
12 AWG3.31 mm²20 A134.39 V (28.0%)345.6 V221.69 V (46.19%)40736.2 WDrop/Amp High
10 AWG5.26 mm²30 A84.57 V (17.62%)395.4 V139.5 V (29.06%)25634.4 WDrop/Amp High
8 AWG8.37 mm²50 A53.15 V (11.07%)426.9 V87.67 V (18.26%)16109.5 WDrop/Amp High
6 AWG13.3 mm²65 A33.45 V (6.97%)446.6 V55.17 V (11.49%)10138.1 WDrop/Amp High
4 AWG21.15 mm²85 A21.03 V (4.38%)459.0 V34.69 V (7.23%)6375.3 WDrop/Amp High
3 AWG26.67 mm²100 A16.68 V (3.47%)463.3 V27.51 V (5.73%)5055.7 WDrop/Amp High
2 AWG33.62 mm²115 A13.23 V (2.76%)466.8 V21.83 V (4.55%)4010.6 WDrop/Amp High
1 AWG42.41 mm²130 A10.49 V (2.19%)469.5 V17.3 V (3.6%)3179.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A8.32 V (1.73%)471.7 V13.72 V (2.86%)2520.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A6.6 V (1.37%)473.4 V10.88 V (2.27%)1999.7 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A5.23 V (1.09%)474.8 V8.63 V (1.8%)1586.1 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A4.15 V (0.86%)475.9 V6.85 V (1.43%)1257.8 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A3.51 V (0.73%)476.5 V5.79 V (1.21%)1064.2 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.93 V (0.61%)477.1 V4.83 V (1.01%)887.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.51 V (0.52%)477.5 V4.14 V (0.86%)760.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.19 V (0.46%)477.8 V3.62 V (0.75%)665.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.76 V (0.37%)478.2 V2.9 V (0.6%)532.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.46 V (0.3%)478.5 V2.41 V (0.5%)443.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.17 V (0.24%)478.8 V1.93 V (0.4%)354.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.88 V (0.18%)479.1 V1.45 V (0.3%)266.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 175 amps at 225 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 175A load over 225 feet one-way at 480V (3-Phase), you need 2/0 AWG copper wire. This produces a voltage drop of 6.6V (1.37%) and delivers 473.4V at the load.

What size aluminum wire is required for 175 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 4/0 AWG to maintain voltage drop at 6.85V (1.43%).

What breaker size is needed for a 175A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (175A × 1.25 = 218.8A), which corresponds to a standard 225A circuit breaker.