⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

175 Amp Wire Size at 750 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 175 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)4/0 AWG107.2 mm² · Drop: 2.88%
Aluminum Wire (≤3% Drop)350 kcmilDrop: 13.8V (2.87%)
Voltage at Load End466.2 VLoss: 13.83 V (4192.7 W)
Power & Breaker (125%)145.49 kW225A Breaker Recommended

All AWG & kcmil Wire Gauges for 175 Amps at 750 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A712.89 V (148.52%)0.0 V1175.94 V (244.99%)216084.7 WDrop/Amp High
12 AWG3.31 mm²20 A447.98 V (93.33%)32.0 V738.96 V (153.95%)135787.4 WDrop/Amp High
10 AWG5.26 mm²30 A281.91 V (58.73%)198.1 V465.01 V (96.88%)85447.9 WDrop/Amp High
8 AWG8.37 mm²50 A177.16 V (36.91%)302.8 V292.23 V (60.88%)53698.5 WDrop/Amp High
6 AWG13.3 mm²65 A111.49 V (23.23%)368.5 V183.91 V (38.31%)33793.7 WDrop/Amp High
4 AWG21.15 mm²85 A70.11 V (14.61%)409.9 V115.65 V (24.09%)21250.9 WDrop/Amp High
3 AWG26.67 mm²100 A55.6 V (11.58%)424.4 V91.71 V (19.11%)16852.5 WDrop/Amp High
2 AWG33.62 mm²115 A44.11 V (9.19%)435.9 V72.75 V (15.16%)13368.7 WDrop/Amp High
1 AWG42.41 mm²130 A34.96 V (7.28%)445.0 V57.67 V (12.02%)10597.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A27.72 V (5.78%)452.3 V45.73 V (9.53%)8402.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A21.99 V (4.58%)458.0 V36.27 V (7.56%)6665.5 W~ ≤5%
3/0 AWG85.01 mm²200 A17.44 V (3.63%)462.6 V28.77 V (5.99%)5287.1 W~ ≤5%
4/0 AWG107.2 mm²230 A13.83 V (2.88%)466.2 V22.82 V (4.75%)4192.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A11.7 V (2.44%)468.3 V19.31 V (4.02%)3547.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A9.76 V (2.03%)470.2 V16.09 V (3.35%)2956.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A8.36 V (1.74%)471.6 V13.8 V (2.87%)2535.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A7.32 V (1.52%)472.7 V12.07 V (2.51%)2217.3 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A5.85 V (1.22%)474.1 V9.65 V (2.01%)1773.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A4.88 V (1.02%)475.1 V8.05 V (1.68%)1478.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A3.9 V (0.81%)476.1 V6.44 V (1.34%)1182.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.93 V (0.61%)477.1 V4.83 V (1.01%)887.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 175 amps at 750 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 175A load over 750 feet one-way at 480V (3-Phase), you need 4/0 AWG copper wire. This produces a voltage drop of 13.83V (2.88%) and delivers 466.2V at the load.

What size aluminum wire is required for 175 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 350 kcmil to maintain voltage drop at 13.8V (2.87%).

What breaker size is needed for a 175A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (175A × 1.25 = 218.8A), which corresponds to a standard 225A circuit breaker.