🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

175 Amp Wire Size at 800 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 175 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.5%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 5.95V (4.95%)
Voltage at Load End118.2 VLoss: 1.8 V (315.4 W)
Power & Breaker (125%)21.0 kW225A Breaker Recommended

All AWG & kcmil Wire Gauges for 175 Amps at 800 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A878.06 V (731.72%)0.0 V1448.39 V (1206.99%)153660.2 WDrop/Amp High
12 AWG3.31 mm²20 A551.77 V (459.81%)0.0 V910.16 V (758.47%)96559.9 WDrop/Amp High
10 AWG5.26 mm²30 A347.22 V (289.35%)0.0 V572.75 V (477.29%)60763.0 WDrop/Amp High
8 AWG8.37 mm²50 A218.2 V (181.84%)0.0 V359.93 V (299.94%)38185.6 WDrop/Amp High
6 AWG13.3 mm²65 A137.32 V (114.43%)0.0 V226.51 V (188.76%)24031.1 WDrop/Amp High
4 AWG21.15 mm²85 A86.35 V (71.96%)33.6 V142.44 V (118.7%)15111.7 WDrop/Amp High
3 AWG26.67 mm²100 A68.48 V (57.07%)51.5 V112.96 V (94.13%)11984.0 WDrop/Amp High
2 AWG33.62 mm²115 A54.32 V (45.27%)65.7 V89.61 V (74.67%)9506.6 WDrop/Amp High
1 AWG42.41 mm²130 A43.06 V (35.89%)76.9 V71.04 V (59.2%)7536.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A34.14 V (28.45%)85.9 V56.32 V (46.93%)5975.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A27.09 V (22.57%)92.9 V44.68 V (37.23%)4739.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A21.48 V (17.9%)98.5 V35.44 V (29.53%)3759.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A17.04 V (14.2%)103.0 V28.1 V (23.42%)2981.5 WDrop/Amp High
250 kcmil126.7 mm²255 A14.41 V (12.01%)105.6 V23.78 V (19.81%)2522.6 WDrop/Amp High
300 kcmil152.0 mm²285 A12.02 V (10.01%)108.0 V19.82 V (16.52%)2102.7 WDrop/Amp High
350 kcmil177.3 mm²310 A10.3 V (8.58%)109.7 V16.99 V (14.16%)1802.7 WDrop/Amp High
400 kcmil202.7 mm²335 A9.01 V (7.51%)111.0 V14.86 V (12.39%)1576.8 WDrop/Amp High
500 kcmil253.4 mm²380 A7.21 V (6.01%)112.8 V11.89 V (9.91%)1261.3 WDrop/Amp High
600 kcmil304.0 mm²420 A6.01 V (5.01%)114.0 V9.91 V (8.26%)1051.4 WDrop/Amp High
750 kcmil380.0 mm²475 A4.81 V (4.01%)115.2 V7.93 V (6.61%)841.1 W~ ≤5%
1000 kcmil506.7 mm²545 A3.6 V (3.0%)116.4 V5.95 V (4.95%)630.8 W~ ≤5%

Frequently Asked Engineering Questions

What size copper wire do I need for 175 amps at 800 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 175A load over 800 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.8V (1.5%) and delivers 118.2V at the load.

What size aluminum wire is required for 175 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 5.95V (4.95%).

What breaker size is needed for a 175A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (175A × 1.25 = 218.8A), which corresponds to a standard 225A circuit breaker.