⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

20 Amp Wire Size at 275 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 20 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)10 AWG5.26 mm² · Drop: 2.46%
Aluminum Wire (≤3% Drop)8 AWGDrop: 12.25V (2.55%)
Voltage at Load End468.2 VLoss: 11.81 V (409.2 W)
Power & Breaker (125%)16.63 kW25A Breaker Recommended

All AWG & kcmil Wire Gauges for 20 Amps at 275 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A29.87 V (6.22%)450.1 V49.28 V (10.27%)1034.9 WDrop/Amp High
12 AWG3.31 mm²20 A18.77 V (3.91%)461.2 V30.97 V (6.45%)650.3 W~ ≤5%
10 AWG5.26 mm²30 A11.81 V (2.46%)468.2 V19.49 V (4.06%)409.2 W✓ PASS (≤3%)
8 AWG8.37 mm²50 A7.42 V (1.55%)472.6 V12.25 V (2.55%)257.2 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A4.67 V (0.97%)475.3 V7.71 V (1.61%)161.8 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A2.94 V (0.61%)477.1 V4.85 V (1.01%)101.8 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A2.33 V (0.49%)477.7 V3.84 V (0.8%)80.7 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.85 V (0.39%)478.2 V3.05 V (0.64%)64.0 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.47 V (0.31%)478.5 V2.42 V (0.5%)50.8 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.16 V (0.24%)478.8 V1.92 V (0.4%)40.2 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.92 V (0.19%)479.1 V1.52 V (0.32%)31.9 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.73 V (0.15%)479.3 V1.21 V (0.25%)25.3 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.58 V (0.12%)479.4 V0.96 V (0.2%)20.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.49 V (0.1%)479.5 V0.81 V (0.17%)17.0 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.41 V (0.09%)479.6 V0.67 V (0.14%)14.2 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.35 V (0.07%)479.6 V0.58 V (0.12%)12.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.31 V (0.06%)479.7 V0.51 V (0.11%)10.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.25 V (0.05%)479.8 V0.4 V (0.08%)8.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.2 V (0.04%)479.8 V0.34 V (0.07%)7.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.16 V (0.03%)479.8 V0.27 V (0.06%)5.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.12 V (0.03%)479.9 V0.2 V (0.04%)4.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 20 amps at 275 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 20A load over 275 feet one-way at 480V (3-Phase), you need 10 AWG copper wire. This produces a voltage drop of 11.81V (2.46%) and delivers 468.2V at the load.

What size aluminum wire is required for 20 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 8 AWG to maintain voltage drop at 12.25V (2.55%).

What breaker size is needed for a 20A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (20A × 1.25 = 25.0A), which corresponds to a standard 25A circuit breaker.