🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

30 Amp Wire Size at 275 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 30 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 2.32%
Aluminum Wire (≤3% Drop)6 AWGDrop: 11.56V (2.41%)
Voltage at Load End468.9 VLoss: 11.14 V (578.6 W)
Power & Breaker (125%)24.94 kW40A Breaker Recommended

All AWG & kcmil Wire Gauges for 30 Amps at 275 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A44.81 V (9.34%)435.2 V73.92 V (15.4%)2328.4 WDrop/Amp High
12 AWG3.31 mm²20 A28.16 V (5.87%)451.8 V46.45 V (9.68%)1463.2 WDrop/Amp High
10 AWG5.26 mm²30 A17.72 V (3.69%)462.3 V29.23 V (6.09%)920.7 W~ ≤5%
8 AWG8.37 mm²50 A11.14 V (2.32%)468.9 V18.37 V (3.83%)578.6 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A7.01 V (1.46%)473.0 V11.56 V (2.41%)364.1 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A4.41 V (0.92%)475.6 V7.27 V (1.51%)229.0 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A3.49 V (0.73%)476.5 V5.76 V (1.2%)181.6 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A2.77 V (0.58%)477.2 V4.57 V (0.95%)144.1 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A2.2 V (0.46%)477.8 V3.63 V (0.76%)114.2 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.74 V (0.36%)478.3 V2.87 V (0.6%)90.5 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.38 V (0.29%)478.6 V2.28 V (0.48%)71.8 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.1 V (0.23%)478.9 V1.81 V (0.38%)57.0 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.87 V (0.18%)479.1 V1.43 V (0.3%)45.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.74 V (0.15%)479.3 V1.21 V (0.25%)38.2 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.61 V (0.13%)479.4 V1.01 V (0.21%)31.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.53 V (0.11%)479.5 V0.87 V (0.18%)27.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.46 V (0.1%)479.5 V0.76 V (0.16%)23.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.37 V (0.08%)479.6 V0.61 V (0.13%)19.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.31 V (0.06%)479.7 V0.51 V (0.11%)15.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.25 V (0.05%)479.8 V0.4 V (0.08%)12.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.18 V (0.04%)479.8 V0.3 V (0.06%)9.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 30 amps at 275 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 30A load over 275 feet one-way at 480V (3-Phase), you need 8 AWG copper wire. This produces a voltage drop of 11.14V (2.32%) and delivers 468.9V at the load.

What size aluminum wire is required for 30 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 11.56V (2.41%).

What breaker size is needed for a 30A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (30A × 1.25 = 37.5A), which corresponds to a standard 40A circuit breaker.