⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

80 Amp Wire Size at 275 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 80 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 2.45%
Aluminum Wire (≤3% Drop)2 AWGDrop: 12.19V (2.54%)
Voltage at Load End468.2 VLoss: 11.75 V (1628.4 W)
Power & Breaker (125%)66.51 kW100A Breaker Recommended

All AWG & kcmil Wire Gauges for 80 Amps at 275 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A119.49 V (24.89%)360.5 V197.11 V (41.06%)16557.7 WDrop/Amp High
12 AWG3.31 mm²20 A75.09 V (15.64%)404.9 V123.86 V (25.8%)10404.8 WDrop/Amp High
10 AWG5.26 mm²30 A47.25 V (9.84%)432.7 V77.94 V (16.24%)6547.5 WDrop/Amp High
8 AWG8.37 mm²50 A29.7 V (6.19%)450.3 V48.98 V (10.2%)4114.7 WDrop/Amp High
6 AWG13.3 mm²65 A18.69 V (3.89%)461.3 V30.83 V (6.42%)2589.5 WDrop/Amp High
4 AWG21.15 mm²85 A11.75 V (2.45%)468.2 V19.38 V (4.04%)1628.4 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A9.32 V (1.94%)470.7 V15.37 V (3.2%)1291.3 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A7.39 V (1.54%)472.6 V12.19 V (2.54%)1024.4 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A5.86 V (1.22%)474.1 V9.67 V (2.01%)812.1 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A4.65 V (0.97%)475.4 V7.66 V (1.6%)643.9 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A3.69 V (0.77%)476.3 V6.08 V (1.27%)510.8 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A2.92 V (0.61%)477.1 V4.82 V (1.0%)405.1 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A2.32 V (0.48%)477.7 V3.82 V (0.8%)321.3 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.96 V (0.41%)478.0 V3.24 V (0.67%)271.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.64 V (0.34%)478.4 V2.7 V (0.56%)226.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.4 V (0.29%)478.6 V2.31 V (0.48%)194.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.23 V (0.26%)478.8 V2.02 V (0.42%)169.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.98 V (0.2%)479.0 V1.62 V (0.34%)135.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.82 V (0.17%)479.2 V1.35 V (0.28%)113.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.65 V (0.14%)479.3 V1.08 V (0.22%)90.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.49 V (0.1%)479.5 V0.81 V (0.17%)68.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 80 amps at 275 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 80A load over 275 feet one-way at 480V (3-Phase), you need 4 AWG copper wire. This produces a voltage drop of 11.75V (2.45%) and delivers 468.2V at the load.

What size aluminum wire is required for 80 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 2 AWG to maintain voltage drop at 12.19V (2.54%).

What breaker size is needed for a 80A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (80A × 1.25 = 100.0A), which corresponds to a standard 100A circuit breaker.