🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

225 Amp Wire Size at 225 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 225 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)4/0 AWG107.2 mm² · Drop: 2.22%
Aluminum Wire (≤3% Drop)300 kcmilDrop: 6.21V (2.59%)
Voltage at Load End234.7 VLoss: 5.34 V (2079.2 W)
Power & Breaker (125%)93.53 kW300A Breaker Recommended

All AWG & kcmil Wire Gauges for 225 Amps at 225 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A274.97 V (114.57%)0.0 V453.58 V (188.99%)107160.4 WDrop/Amp High
12 AWG3.31 mm²20 A172.79 V (72.0%)67.2 V285.03 V (118.76%)67339.4 WDrop/Amp High
10 AWG5.26 mm²30 A108.73 V (45.31%)131.3 V179.36 V (74.73%)42375.2 WDrop/Amp High
8 AWG8.37 mm²50 A68.33 V (28.47%)171.7 V112.72 V (46.97%)26630.1 WDrop/Amp High
6 AWG13.3 mm²65 A43.0 V (17.92%)197.0 V70.94 V (29.56%)16758.9 WDrop/Amp High
4 AWG21.15 mm²85 A27.04 V (11.27%)213.0 V44.61 V (18.59%)10538.7 WDrop/Amp High
3 AWG26.67 mm²100 A21.45 V (8.94%)218.6 V35.37 V (14.74%)8357.5 WDrop/Amp High
2 AWG33.62 mm²115 A17.01 V (7.09%)223.0 V28.06 V (11.69%)6629.8 WDrop/Amp High
1 AWG42.41 mm²130 A13.49 V (5.62%)226.5 V22.25 V (9.27%)5255.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A10.69 V (4.46%)229.3 V17.64 V (7.35%)4167.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A8.48 V (3.53%)231.5 V13.99 V (5.83%)3305.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A6.73 V (2.8%)233.3 V11.1 V (4.62%)2622.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.34 V (2.22%)234.7 V8.8 V (3.67%)2079.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A4.51 V (1.88%)235.5 V7.45 V (3.1%)1759.2 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A3.76 V (1.57%)236.2 V6.21 V (2.59%)1466.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A3.23 V (1.34%)236.8 V5.32 V (2.22%)1257.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.82 V (1.18%)237.2 V4.65 V (1.94%)1099.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.26 V (0.94%)237.7 V3.72 V (1.55%)879.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.88 V (0.78%)238.1 V3.1 V (1.29%)733.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.51 V (0.63%)238.5 V2.48 V (1.03%)586.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.13 V (0.47%)238.9 V1.86 V (0.78%)439.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 225 amps at 225 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 225A load over 225 feet one-way at 240V (3-Phase), you need 4/0 AWG copper wire. This produces a voltage drop of 5.34V (2.22%) and delivers 234.7V at the load.

What size aluminum wire is required for 225 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 300 kcmil to maintain voltage drop at 6.21V (2.59%).

What breaker size is needed for a 225A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (225A × 1.25 = 281.2A), which corresponds to a standard 300A circuit breaker.