⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

225 Amp Wire Size at 450 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 225 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)8× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.71%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 4.3V (35.83%)
Voltage at Load End11.7 VLoss: 0.33 V (73.3 W)
Power & Breaker (125%)2.7 kW300A Breaker Recommended

All AWG & kcmil Wire Gauges for 225 Amps at 450 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A635.02 V (5291.87%)0.0 V1047.49 V (8729.11%)142880.5 WDrop/Amp High
12 AWG3.31 mm²20 A399.05 V (3325.4%)0.0 V658.24 V (5485.36%)89785.9 WDrop/Amp High
10 AWG5.26 mm²30 A251.11 V (2092.6%)0.0 V414.22 V (3451.82%)56500.3 WDrop/Amp High
8 AWG8.37 mm²50 A157.81 V (1315.06%)0.0 V260.31 V (2169.24%)35506.7 WDrop/Amp High
6 AWG13.3 mm²65 A99.31 V (827.6%)0.0 V163.82 V (1365.15%)22345.2 WDrop/Amp High
4 AWG21.15 mm²85 A62.45 V (520.43%)0.0 V103.02 V (858.47%)14051.6 WDrop/Amp High
3 AWG26.67 mm²100 A49.53 V (412.71%)0.0 V81.69 V (680.79%)11143.3 WDrop/Amp High
2 AWG33.62 mm²115 A39.29 V (327.4%)0.0 V64.81 V (540.05%)8839.7 WDrop/Amp High
1 AWG42.41 mm²130 A31.14 V (259.54%)0.0 V51.37 V (428.12%)7007.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A24.69 V (205.78%)0.0 V40.73 V (339.44%)5556.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A19.59 V (163.24%)0.0 V32.31 V (269.27%)4407.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A15.54 V (129.48%)0.0 V25.63 V (213.58%)3496.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A12.32 V (102.68%)0.0 V20.32 V (169.37%)2772.3 WDrop/Amp High
250 kcmil126.7 mm²255 A10.43 V (86.88%)1.6 V17.2 V (143.3%)2345.6 WDrop/Amp High
300 kcmil152.0 mm²285 A8.69 V (72.42%)3.3 V14.33 V (119.45%)1955.2 WDrop/Amp High
350 kcmil177.3 mm²310 A7.45 V (62.08%)4.6 V12.29 V (102.41%)1676.2 WDrop/Amp High
400 kcmil202.7 mm²335 A6.52 V (54.3%)5.5 V10.75 V (89.57%)1466.2 WDrop/Amp High
500 kcmil253.4 mm²380 A5.21 V (43.44%)6.8 V8.6 V (71.65%)1172.8 WDrop/Amp High
600 kcmil304.0 mm²420 A4.34 V (36.21%)7.7 V7.17 V (59.73%)977.6 WDrop/Amp High
750 kcmil380.0 mm²475 A3.48 V (28.97%)8.5 V5.73 V (47.78%)782.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.61 V (21.72%)9.4 V4.3 V (35.83%)586.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 225 amps at 450 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 225A load over 450 feet one-way at 12V (DC), you need 8× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.33V (2.71%) and delivers 11.7V at the load.

What size aluminum wire is required for 225 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 4.3V (35.83%).

What breaker size is needed for a 225A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (225A × 1.25 = 281.2A), which corresponds to a standard 300A circuit breaker.