🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

225 Amp Wire Size at 600 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 225 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 2.9%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 5.73V (4.78%)
Voltage at Load End116.5 VLoss: 3.48 V (782.0 W)
Power & Breaker (125%)27.0 kW300A Breaker Recommended

All AWG & kcmil Wire Gauges for 225 Amps at 600 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A846.7 V (705.58%)0.0 V1396.66 V (1163.88%)190507.3 WDrop/Amp High
12 AWG3.31 mm²20 A532.06 V (443.39%)0.0 V877.66 V (731.38%)119714.6 WDrop/Amp High
10 AWG5.26 mm²30 A334.82 V (279.01%)0.0 V552.29 V (460.24%)75333.7 WDrop/Amp High
8 AWG8.37 mm²50 A210.41 V (175.34%)0.0 V347.08 V (289.23%)47342.3 WDrop/Amp High
6 AWG13.3 mm²65 A132.42 V (110.35%)0.0 V218.42 V (182.02%)29793.6 WDrop/Amp High
4 AWG21.15 mm²85 A83.27 V (69.39%)36.7 V137.35 V (114.46%)18735.5 WDrop/Amp High
3 AWG26.67 mm²100 A66.03 V (55.03%)54.0 V108.93 V (90.77%)14857.7 WDrop/Amp High
2 AWG33.62 mm²115 A52.38 V (43.65%)67.6 V86.41 V (72.01%)11786.3 WDrop/Amp High
1 AWG42.41 mm²130 A41.53 V (34.61%)78.5 V68.5 V (57.08%)9343.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A32.92 V (27.44%)87.1 V54.31 V (45.26%)7408.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A26.12 V (21.76%)93.9 V43.08 V (35.9%)5876.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A20.72 V (17.26%)99.3 V34.17 V (28.48%)4661.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A16.43 V (13.69%)103.6 V27.1 V (22.58%)3696.4 WDrop/Amp High
250 kcmil126.7 mm²255 A13.9 V (11.58%)106.1 V22.93 V (19.11%)3127.5 WDrop/Amp High
300 kcmil152.0 mm²285 A11.59 V (9.66%)108.4 V19.11 V (15.93%)2606.9 WDrop/Amp High
350 kcmil177.3 mm²310 A9.93 V (8.28%)110.1 V16.38 V (13.65%)2234.9 WDrop/Amp High
400 kcmil202.7 mm²335 A8.69 V (7.24%)111.3 V14.33 V (11.94%)1954.9 WDrop/Amp High
500 kcmil253.4 mm²380 A6.95 V (5.79%)113.0 V11.46 V (9.55%)1563.8 WDrop/Amp High
600 kcmil304.0 mm²420 A5.79 V (4.83%)114.2 V9.56 V (7.96%)1303.5 W~ ≤5%
750 kcmil380.0 mm²475 A4.63 V (3.86%)115.4 V7.64 V (6.37%)1042.8 W~ ≤5%
1000 kcmil506.7 mm²545 A3.48 V (2.9%)116.5 V5.73 V (4.78%)782.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 225 amps at 600 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 225A load over 600 feet one-way at 120V (1-Phase), you need 1000 kcmil copper wire. This produces a voltage drop of 3.48V (2.9%) and delivers 116.5V at the load.

What size aluminum wire is required for 225 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 5.73V (4.78%).

What breaker size is needed for a 225A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (225A × 1.25 = 281.2A), which corresponds to a standard 300A circuit breaker.