⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

25 Amp Wire Size at 175 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 25 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)350 kcmil177.3 mm² · Drop: 2.68%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 0.31V (2.58%)
Voltage at Load End11.7 VLoss: 0.32 V (8.0 W)
Power & Breaker (125%)0.3 kW32A Breaker Recommended

All AWG & kcmil Wire Gauges for 25 Amps at 175 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A27.44 V (228.66%)0.0 V45.26 V (377.18%)686.0 WDrop/Amp High
12 AWG3.31 mm²20 A17.24 V (143.69%)0.0 V28.44 V (237.02%)431.1 WDrop/Amp High
10 AWG5.26 mm²30 A10.85 V (90.42%)1.1 V17.9 V (149.15%)271.3 WDrop/Amp High
8 AWG8.37 mm²50 A6.82 V (56.82%)5.2 V11.25 V (93.73%)170.5 WDrop/Amp High
6 AWG13.3 mm²65 A4.29 V (35.76%)7.7 V7.08 V (58.99%)107.3 WDrop/Amp High
4 AWG21.15 mm²85 A2.7 V (22.49%)9.3 V4.45 V (37.09%)67.5 WDrop/Amp High
3 AWG26.67 mm²100 A2.14 V (17.83%)9.9 V3.53 V (29.42%)53.5 WDrop/Amp High
2 AWG33.62 mm²115 A1.7 V (14.15%)10.3 V2.8 V (23.34%)42.4 WDrop/Amp High
1 AWG42.41 mm²130 A1.35 V (11.21%)10.7 V2.22 V (18.5%)33.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A1.07 V (8.89%)10.9 V1.76 V (14.67%)26.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A0.85 V (7.05%)11.2 V1.4 V (11.63%)21.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A0.67 V (5.59%)11.3 V1.11 V (9.23%)16.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A0.53 V (4.44%)11.5 V0.88 V (7.32%)13.3 W~ ≤5%
250 kcmil126.7 mm²255 A0.45 V (3.75%)11.5 V0.74 V (6.19%)11.3 W~ ≤5%
300 kcmil152.0 mm²285 A0.38 V (3.13%)11.6 V0.62 V (5.16%)9.4 W~ ≤5%
350 kcmil177.3 mm²310 A0.32 V (2.68%)11.7 V0.53 V (4.42%)8.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.28 V (2.35%)11.7 V0.46 V (3.87%)7.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.23 V (1.88%)11.8 V0.37 V (3.1%)5.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.19 V (1.56%)11.8 V0.31 V (2.58%)4.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.15 V (1.25%)11.8 V0.25 V (2.06%)3.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.11 V (0.94%)11.9 V0.19 V (1.55%)2.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 25 amps at 175 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 25A load over 175 feet one-way at 12V (DC), you need 350 kcmil copper wire. This produces a voltage drop of 0.32V (2.68%) and delivers 11.7V at the load.

What size aluminum wire is required for 25 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 0.31V (2.58%).

What breaker size is needed for a 25A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (25A × 1.25 = 31.2A), which corresponds to a standard 32A circuit breaker.