🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

25 Amp Wire Size at 125 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 25 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)250 kcmil126.7 mm² · Drop: 2.68%
Aluminum Wire (≤3% Drop)400 kcmilDrop: 0.33V (2.76%)
Voltage at Load End11.7 VLoss: 0.32 V (8.0 W)
Power & Breaker (125%)0.3 kW32A Breaker Recommended

All AWG & kcmil Wire Gauges for 25 Amps at 125 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A19.6 V (163.33%)0.0 V32.33 V (269.42%)490.0 WDrop/Amp High
12 AWG3.31 mm²20 A12.32 V (102.64%)0.0 V20.32 V (169.3%)307.9 WDrop/Amp High
10 AWG5.26 mm²30 A7.75 V (64.59%)4.2 V12.78 V (106.54%)193.8 WDrop/Amp High
8 AWG8.37 mm²50 A4.87 V (40.59%)7.1 V8.03 V (66.95%)121.8 WDrop/Amp High
6 AWG13.3 mm²65 A3.07 V (25.54%)8.9 V5.06 V (42.13%)76.6 WDrop/Amp High
4 AWG21.15 mm²85 A1.93 V (16.06%)10.1 V3.18 V (26.5%)48.2 WDrop/Amp High
3 AWG26.67 mm²100 A1.53 V (12.74%)10.5 V2.52 V (21.01%)38.2 WDrop/Amp High
2 AWG33.62 mm²115 A1.21 V (10.1%)10.8 V2.0 V (16.67%)30.3 WDrop/Amp High
1 AWG42.41 mm²130 A0.96 V (8.01%)11.0 V1.59 V (13.21%)24.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A0.76 V (6.35%)11.2 V1.26 V (10.48%)19.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A0.6 V (5.04%)11.4 V1.0 V (8.31%)15.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A0.48 V (4.0%)11.5 V0.79 V (6.59%)12.0 W~ ≤5%
4/0 AWG107.2 mm²230 A0.38 V (3.17%)11.6 V0.63 V (5.23%)9.5 W~ ≤5%
250 kcmil126.7 mm²255 A0.32 V (2.68%)11.7 V0.53 V (4.42%)8.0 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.27 V (2.24%)11.7 V0.44 V (3.69%)6.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.23 V (1.92%)11.8 V0.38 V (3.16%)5.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.2 V (1.68%)11.8 V0.33 V (2.76%)5.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.16 V (1.34%)11.8 V0.27 V (2.21%)4.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.13 V (1.12%)11.9 V0.22 V (1.84%)3.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.11 V (0.89%)11.9 V0.18 V (1.47%)2.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.08 V (0.67%)11.9 V0.13 V (1.11%)2.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 25 amps at 125 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 25A load over 125 feet one-way at 12V (DC), you need 250 kcmil copper wire. This produces a voltage drop of 0.32V (2.68%) and delivers 11.7V at the load.

What size aluminum wire is required for 25 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 400 kcmil to maintain voltage drop at 0.33V (2.76%).

What breaker size is needed for a 25A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (25A × 1.25 = 31.2A), which corresponds to a standard 32A circuit breaker.