⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

25 Amp Wire Size at 30 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 25 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)2 AWG33.62 mm² · Drop: 2.43%
Aluminum Wire (≤3% Drop)1/0 AWGDrop: 0.3V (2.51%)
Voltage at Load End11.7 VLoss: 0.29 V (7.3 W)
Power & Breaker (125%)0.3 kW32A Breaker Recommended

All AWG & kcmil Wire Gauges for 25 Amps at 30 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A4.7 V (39.2%)7.3 V7.76 V (64.66%)117.6 WDrop/Amp High
12 AWG3.31 mm²20 A2.96 V (24.63%)9.0 V4.88 V (40.63%)73.9 WDrop/Amp High
10 AWG5.26 mm²30 A1.86 V (15.5%)10.1 V3.07 V (25.57%)46.5 WDrop/Amp High
8 AWG8.37 mm²50 A1.17 V (9.74%)10.8 V1.93 V (16.07%)29.2 WDrop/Amp High
6 AWG13.3 mm²65 A0.74 V (6.13%)11.3 V1.21 V (10.11%)18.4 WDrop/Amp High
4 AWG21.15 mm²85 A0.46 V (3.86%)11.5 V0.76 V (6.36%)11.6 W~ ≤5%
3 AWG26.67 mm²100 A0.37 V (3.06%)11.6 V0.61 V (5.04%)9.2 W~ ≤5%
2 AWG33.62 mm²115 A0.29 V (2.43%)11.7 V0.48 V (4.0%)7.3 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.23 V (1.92%)11.8 V0.38 V (3.17%)5.8 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.18 V (1.52%)11.8 V0.3 V (2.51%)4.6 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.15 V (1.21%)11.9 V0.24 V (1.99%)3.6 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.12 V (0.96%)11.9 V0.19 V (1.58%)2.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.09 V (0.76%)11.9 V0.15 V (1.25%)2.3 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.08 V (0.64%)11.9 V0.13 V (1.06%)1.9 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.06 V (0.54%)11.9 V0.11 V (0.88%)1.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.06 V (0.46%)11.9 V0.09 V (0.76%)1.4 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.05 V (0.4%)12.0 V0.08 V (0.66%)1.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.04 V (0.32%)12.0 V0.06 V (0.53%)1.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.03 V (0.27%)12.0 V0.05 V (0.44%)0.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.03 V (0.21%)12.0 V0.04 V (0.35%)0.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.02 V (0.16%)12.0 V0.03 V (0.27%)0.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 25 amps at 30 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 25A load over 30 feet one-way at 12V (DC), you need 2 AWG copper wire. This produces a voltage drop of 0.29V (2.43%) and delivers 11.7V at the load.

What size aluminum wire is required for 25 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 1/0 AWG to maintain voltage drop at 0.3V (2.51%).

What breaker size is needed for a 25A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (25A × 1.25 = 31.2A), which corresponds to a standard 32A circuit breaker.