🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

25 Amp Wire Size at 225 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 25 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 2.41%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 0.32V (2.65%)
Voltage at Load End11.7 VLoss: 0.29 V (7.2 W)
Power & Breaker (125%)0.3 kW32A Breaker Recommended

All AWG & kcmil Wire Gauges for 25 Amps at 225 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A35.28 V (293.99%)0.0 V58.19 V (484.95%)882.0 WDrop/Amp High
12 AWG3.31 mm²20 A22.17 V (184.74%)0.0 V36.57 V (304.74%)554.2 WDrop/Amp High
10 AWG5.26 mm²30 A13.95 V (116.26%)0.0 V23.01 V (191.77%)348.8 WDrop/Amp High
8 AWG8.37 mm²50 A8.77 V (73.06%)3.2 V14.46 V (120.51%)219.2 WDrop/Amp High
6 AWG13.3 mm²65 A5.52 V (45.98%)6.5 V9.1 V (75.84%)137.9 WDrop/Amp High
4 AWG21.15 mm²85 A3.47 V (28.91%)8.5 V5.72 V (47.69%)86.7 WDrop/Amp High
3 AWG26.67 mm²100 A2.75 V (22.93%)9.2 V4.54 V (37.82%)68.8 WDrop/Amp High
2 AWG33.62 mm²115 A2.18 V (18.19%)9.8 V3.6 V (30.0%)54.6 WDrop/Amp High
1 AWG42.41 mm²130 A1.73 V (14.42%)10.3 V2.85 V (23.78%)43.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A1.37 V (11.43%)10.6 V2.26 V (18.86%)34.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.09 V (9.07%)10.9 V1.8 V (14.96%)27.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A0.86 V (7.19%)11.1 V1.42 V (11.87%)21.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A0.68 V (5.7%)11.3 V1.13 V (9.41%)17.1 WDrop/Amp High
250 kcmil126.7 mm²255 A0.58 V (4.83%)11.4 V0.96 V (7.96%)14.5 W~ ≤5%
300 kcmil152.0 mm²285 A0.48 V (4.02%)11.5 V0.8 V (6.64%)12.1 W~ ≤5%
350 kcmil177.3 mm²310 A0.41 V (3.45%)11.6 V0.68 V (5.69%)10.3 W~ ≤5%
400 kcmil202.7 mm²335 A0.36 V (3.02%)11.6 V0.6 V (4.98%)9.1 W~ ≤5%
500 kcmil253.4 mm²380 A0.29 V (2.41%)11.7 V0.48 V (3.98%)7.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.24 V (2.01%)11.8 V0.4 V (3.32%)6.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.19 V (1.61%)11.8 V0.32 V (2.65%)4.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.14 V (1.21%)11.9 V0.24 V (1.99%)3.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 25 amps at 225 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 25A load over 225 feet one-way at 12V (DC), you need 500 kcmil copper wire. This produces a voltage drop of 0.29V (2.41%) and delivers 11.7V at the load.

What size aluminum wire is required for 25 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 0.32V (2.65%).

What breaker size is needed for a 25A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (25A × 1.25 = 31.2A), which corresponds to a standard 32A circuit breaker.