⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

25 Amp Wire Size at 250 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 25 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)6 AWG13.3 mm² · Drop: 2.55%
Aluminum Wire (≤3% Drop)4 AWGDrop: 6.36V (2.65%)
Voltage at Load End233.9 VLoss: 6.13 V (153.3 W)
Power & Breaker (125%)6.0 kW32A Breaker Recommended

All AWG & kcmil Wire Gauges for 25 Amps at 250 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A39.2 V (16.33%)200.8 V64.66 V (26.94%)980.0 WDrop/Amp High
12 AWG3.31 mm²20 A24.63 V (10.26%)215.4 V40.63 V (16.93%)615.8 WDrop/Amp High
10 AWG5.26 mm²30 A15.5 V (6.46%)224.5 V25.57 V (10.65%)387.5 WDrop/Amp High
8 AWG8.37 mm²50 A9.74 V (4.06%)230.3 V16.07 V (6.7%)243.5 W~ ≤5%
6 AWG13.3 mm²65 A6.13 V (2.55%)233.9 V10.11 V (4.21%)153.3 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A3.86 V (1.61%)236.1 V6.36 V (2.65%)96.4 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A3.06 V (1.27%)236.9 V5.04 V (2.1%)76.4 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A2.43 V (1.01%)237.6 V4.0 V (1.67%)60.6 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.92 V (0.8%)238.1 V3.17 V (1.32%)48.1 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.52 V (0.64%)238.5 V2.51 V (1.05%)38.1 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.21 V (0.5%)238.8 V1.99 V (0.83%)30.2 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.96 V (0.4%)239.0 V1.58 V (0.66%)24.0 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.76 V (0.32%)239.2 V1.25 V (0.52%)19.0 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.64 V (0.27%)239.4 V1.06 V (0.44%)16.1 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.54 V (0.22%)239.5 V0.88 V (0.37%)13.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.46 V (0.19%)239.5 V0.76 V (0.32%)11.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.4 V (0.17%)239.6 V0.66 V (0.28%)10.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.32 V (0.13%)239.7 V0.53 V (0.22%)8.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.27 V (0.11%)239.7 V0.44 V (0.18%)6.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.21 V (0.09%)239.8 V0.35 V (0.15%)5.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.16 V (0.07%)239.8 V0.27 V (0.11%)4.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 25 amps at 250 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 25A load over 250 feet one-way at 240V (1-Phase), you need 6 AWG copper wire. This produces a voltage drop of 6.13V (2.55%) and delivers 233.9V at the load.

What size aluminum wire is required for 25 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 4 AWG to maintain voltage drop at 6.36V (2.65%).

What breaker size is needed for a 25A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (25A × 1.25 = 31.2A), which corresponds to a standard 32A circuit breaker.