🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

25 Amp Wire Size at 250 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 25 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)10 AWG5.26 mm² · Drop: 2.8%
Aluminum Wire (≤3% Drop)8 AWGDrop: 13.92V (2.9%)
Voltage at Load End466.6 VLoss: 13.42 V (581.3 W)
Power & Breaker (125%)20.78 kW32A Breaker Recommended

All AWG & kcmil Wire Gauges for 25 Amps at 250 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A33.95 V (7.07%)446.1 V56.0 V (11.67%)1470.0 WDrop/Amp High
12 AWG3.31 mm²20 A21.33 V (4.44%)458.7 V35.19 V (7.33%)923.7 WDrop/Amp High
10 AWG5.26 mm²30 A13.42 V (2.8%)466.6 V22.14 V (4.61%)581.3 W✓ PASS (≤3%)
8 AWG8.37 mm²50 A8.44 V (1.76%)471.6 V13.92 V (2.9%)365.3 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A5.31 V (1.11%)474.7 V8.76 V (1.82%)229.9 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A3.34 V (0.7%)476.7 V5.51 V (1.15%)144.6 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A2.65 V (0.55%)477.4 V4.37 V (0.91%)114.6 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A2.1 V (0.44%)477.9 V3.46 V (0.72%)90.9 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.66 V (0.35%)478.3 V2.75 V (0.57%)72.1 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.32 V (0.28%)478.7 V2.18 V (0.45%)57.2 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.05 V (0.22%)479.0 V1.73 V (0.36%)45.3 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.83 V (0.17%)479.2 V1.37 V (0.29%)36.0 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.66 V (0.14%)479.3 V1.09 V (0.23%)28.5 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.56 V (0.12%)479.4 V0.92 V (0.19%)24.1 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.46 V (0.1%)479.5 V0.77 V (0.16%)20.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.4 V (0.08%)479.6 V0.66 V (0.14%)17.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.35 V (0.07%)479.7 V0.57 V (0.12%)15.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.28 V (0.06%)479.7 V0.46 V (0.1%)12.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.23 V (0.05%)479.8 V0.38 V (0.08%)10.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.19 V (0.04%)479.8 V0.31 V (0.06%)8.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.14 V (0.03%)479.9 V0.23 V (0.05%)6.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 25 amps at 250 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 25A load over 250 feet one-way at 480V (3-Phase), you need 10 AWG copper wire. This produces a voltage drop of 13.42V (2.8%) and delivers 466.6V at the load.

What size aluminum wire is required for 25 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 8 AWG to maintain voltage drop at 13.92V (2.9%).

What breaker size is needed for a 25A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (25A × 1.25 = 31.2A), which corresponds to a standard 32A circuit breaker.