🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

25 Amp Wire Size at 350 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 25 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)2 AWG33.62 mm² · Drop: 2.83%
Aluminum Wire (≤3% Drop)1/0 AWGDrop: 3.52V (2.93%)
Voltage at Load End116.6 VLoss: 3.4 V (84.9 W)
Power & Breaker (125%)3.0 kW32A Breaker Recommended

All AWG & kcmil Wire Gauges for 25 Amps at 350 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A54.88 V (45.73%)65.1 V90.52 V (75.44%)1372.0 WDrop/Amp High
12 AWG3.31 mm²20 A34.49 V (28.74%)85.5 V56.89 V (47.4%)862.1 WDrop/Amp High
10 AWG5.26 mm²30 A21.7 V (18.08%)98.3 V35.8 V (29.83%)542.5 WDrop/Amp High
8 AWG8.37 mm²50 A13.64 V (11.36%)106.4 V22.5 V (18.75%)340.9 WDrop/Amp High
6 AWG13.3 mm²65 A8.58 V (7.15%)111.4 V14.16 V (11.8%)214.6 WDrop/Amp High
4 AWG21.15 mm²85 A5.4 V (4.5%)114.6 V8.9 V (7.42%)134.9 W~ ≤5%
3 AWG26.67 mm²100 A4.28 V (3.57%)115.7 V7.06 V (5.88%)107.0 W~ ≤5%
2 AWG33.62 mm²115 A3.4 V (2.83%)116.6 V5.6 V (4.67%)84.9 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A2.69 V (2.24%)117.3 V4.44 V (3.7%)67.3 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.13 V (1.78%)117.9 V3.52 V (2.93%)53.3 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.69 V (1.41%)118.3 V2.79 V (2.33%)42.3 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.34 V (1.12%)118.7 V2.21 V (1.85%)33.6 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.06 V (0.89%)118.9 V1.76 V (1.46%)26.6 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.9 V (0.75%)119.1 V1.49 V (1.24%)22.5 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.75 V (0.63%)119.2 V1.24 V (1.03%)18.8 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.64 V (0.54%)119.4 V1.06 V (0.88%)16.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.56 V (0.47%)119.4 V0.93 V (0.77%)14.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.45 V (0.38%)119.5 V0.74 V (0.62%)11.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.38 V (0.31%)119.6 V0.62 V (0.52%)9.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.3 V (0.25%)119.7 V0.5 V (0.41%)7.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.23 V (0.19%)119.8 V0.37 V (0.31%)5.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 25 amps at 350 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 25A load over 350 feet one-way at 120V (1-Phase), you need 2 AWG copper wire. This produces a voltage drop of 3.4V (2.83%) and delivers 116.6V at the load.

What size aluminum wire is required for 25 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 1/0 AWG to maintain voltage drop at 3.52V (2.93%).

What breaker size is needed for a 25A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (25A × 1.25 = 31.2A), which corresponds to a standard 32A circuit breaker.